6.2.10 Maintenance

Table 6.30
Maintenance (MAINT ALARM)
Level 2
Alarm Action
(ACTION)
Due At Engine Hours
(DUE AT ENGINE HOURS)
Alarm Due Date
(ALARM DUE DATE)

6.2.11 Rotary actuator (SGC 121 only)

Table 6.31
General (GENERAL)
Level 2
Actuator Application
(ACTUATOR APPLN)
Actuator Speed
(ACTUATOR SPEED)
Actuator Direction
(ACTUATOR DIRECTION)
Governing Mode
(GOVERNING MODE)
Table 6.32
Engine Start Strategy (ENG START STRGY)
Level 2
Cranking Steps
(CRANKING STEPS)
Initial Low Speed Delay
(INIT LOW SPEED DELAY)
Initial Low Speed
(INIT LOW SPEED)
PID Trigger Speed
(PID TRIGGER SPEED)
Ramp Up Time
(RAMP UP TIME)
PID On Time
(PID ON TIME)
Table 6.33
Generator EGov Config (GEN EGOV CNFG)
Level 2
Set Speed Selection
(SET SPEED SELECTION)
(LBD) Droop
(DROOP)
USER MANUAL 4189341226A UK
Range
None
Notification
Warning
10 to 65000 hours
dd/mm/yyyy
Range
As E-Governor
As Start/Stop Device
1 to 10 x 25 Hz
Clockwise to Stop
Anti clockwise to stop
Fixed Speed
Variable Speed
Range
50 to 5000
0 to 180 s
500 to 1800 RPM
20 to 2800 RPM
1 to 180 s
1 to 180 s
Range
Fixed (0 % Droop)
Load Based Droop
0 to 4 %
Page 36 of 72