Service, commissioning and other support functions

When all diagrams have been generated and code has been transferred, the AS
is able to carry out the automation functions. The following online options are
supported by ES680, which provides:
Dynamic function diagrams, i.e. the analog and binary plant values can be
viewed within a function diagram during online operation. This is an
important feature during commissioning and other testing activities since
no extensive measurements at wiring elements or using the programming
device are required
Fast parameter change: mask parameterizations of any function can be
loaded into the automation processor online without generating code. By
confirming the change the transfer will take place and the changed values
can be observed immediately.
Process values can be simulated and preset by simulating inputs from
transmitters. The TXP system will use the simulated value instead of the
actual input and will ignore faulty ones (No hardware simulation is
required).
Analog and binary values can replace the values calculated by the system
at previously fixed locations using simulation functions blocks (simulb and
simulk).
24