Alternative solutions with AS 620 B (2)
Function modules (FUM) and/or Signal modules (SIM)
FUM - Configuration
FUM - Configuration
AP
AP
I&C room
I&C room

SIM modules

SIM modules are used for the input and output of analog and binary signals.
Their task is to digitize process signals and to output digital settings as binary or
analog signals. More complex tasks such as signal processing, monitoring, and
time-tagging are performed in the AP. A signal module in conjunction with the
associated function block performs the same function as the corresponding FUM.
SIMs are modules from the SIMATIC S5/S7, ET200 B/ET200 M range, which
allows the input and output modules to be installed locally in the process
environment instead of centrally in the automation system. For this purpose, the
modules are combined into stations and located in the immediate vicinity of the
field devices, installed in distribution boxes or wall-mounted housings for
example.
The advantage of a distributed configuration lies in the minimal space
requirements in the computer room, because only the cabinets for the AP are
installed there. Savings can also be made in wiring costs because only the loop-
in cable from the I/O to the nearest station is required.
Distributed configurations also permit the automation processors and the input
and output modules in the process environment to be located a considerable
distance apart. The SIM modules are linked with the automation processor via
PROFIBUS. PROFIBUS can be operated at a maximum data transmission rate
of 1.5 Mbit/s and is also available in a fiber-optic version for use under adverse
interference conditions or where lightning protection is required.
The flexibility of the automation system allows the FUM structure to be combined
with the distributed SIM structure, which supports the implementation of tailor-
made solutions.
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
SIM - Configuration
SIM - Configuration
FUM
FUM
FUM
FUM
Field
Field
Field
JB
JB
JB
JB
M
Centralized
Centralized
Training Center
AP
AP
I&C room
I&C room
Profibus
Profibus
SIM B
SIM B
SIM B
SIM B
M
Distributed
Distributed
TXP-CLC Course
2
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents