Reject to manual (REJ/MAN)

Name: REJ/MAN
Function: Defines whether the operation mode set to manual in the event of a
fault or failure. Can only be activated by enabling TAG-OUT via parameter RMS.
Range of values:
Not activated / activated
Basic setting:
Not activated.

Operation mode (OP_MODE)

Name: OP_MODE
Function: Defines the possible operating modes. Can only be activated by
enabling TAG-OUT via parameter RMS.
Range of values:
AUTO / MAN
SEMI
SEMI / MAN
Basic setting:
AUTO / MAN.

Behavior on switchgear fault (BSFG)

Name: BSFG
Function: Defines whether it is possible to initiate a manual "OFF" command from
OM650 while the switchgear, breaker or motor starter is in fault (SAG). Can only
be activated by enabling TAG-OUT via parameter RMS.
Range of values:
Not activated / activated
Basic setting:
Not activated

Inputs from other logic (not I/O type inputs)

Name
Description
SQ
Group alarm acknowledgement
BL/OM
Block OM operating
BL/AP
Block alarm protection command
A/ON
Auto command on
A/OFF
Auto command off
SGC
Under voltage limit signal
P/ON
Protection command on
P/OFF
Protection command off
EN/ON
Enabling on
EN/OFF
Enabling off
VOS
Local controlling
AUTO
Priority switch man/auto
MAN
Priority switch auto/man
FB/OFF
Feedback off
SGF
Switchgear fault
FB/ON
Feedback on
ANB
Feeder not ready for operation