Feeder Not Ready For Operation (Anb); Outputs From Other Logic (Not I/O Type Outputs); Feedback On (Cb/On); Feedback Off (Cb/Off) - Siemens TXP-CLC Manual

Table of Contents

Advertisement

Feeder not ready for operation (ANB)

This binary input can be used to decouple the hardware from the software and
allow modification to the input signal by additional logic before the signal is
connected to the DCM FB 163. When this input is a binary "1" the DCM receives
feedback that the driven device (breaker, switchgear, etc.) is in a test or racked
out condition. It can be used in place of the hardwired input ANB.

Outputs from other logic (not I/O type outputs)

Name
Description
CB/ON
Actual status on/open (feedback on)
CB/OFF
Actual status off/closed (feedback off)
DS/ON
Desired status on/open
DS/OFF
Desired status off/closed
ZES
Last status reached by protection
ZEA
Last status reached by automatic
ZEH
Last status reached by manual
USZ
Under voltage time running
ULS
Under voltage limit signal
AZB
Feeder ready for operation
NOSD
No status discrepancy error
NOFF
No feeder fault
KLB
No running time / torque alarm
CB/ONN
Actual status not on/open
CB/OFFN
Actual status not off/closed
VOS
Local controlling
P/SIM
PAE_E simulated
BL/COLO
Command logic locked
CB/AUTO
Feed back priority auto/manual

Feedback on (CB/ON)

This output is a logic "1" when the on feed back input (RME) is energized or the
input FB/ON is a binary "1" and the FB163 has no fault conditions.

Feedback off (CB/OFF)

This output is a logic "1" when the off feed back input (RMA) is energized or the
input FB/ON is a binary "1" and the FB163 has no fault conditions.
Desired status on (DS/ON)
This output is a logic "1" from the time On is requested by logic or by operator,
until feed back On is received or DCM is in a fault condition.
Desired status off (DS/OFF)
This output is a logic "1" " from the time Off is requested by logic or by operator,
until feed back Off is received or DCM is in a fault condition.