The signal must be defined (SIGDEF) on the individual level logic diagram
(function plan / YFR) that is identified with the Power Plant Identification Code
(KKS) for the equipment. The signal is then available for use as an output to the
field device. The SIGDEF and KKS must match the output channel identifier in
the parameter mask of the SIM module on the rack level location drawing for the
connection to the output point.
The output signal connection to the hardware from the CAO block must have
YL01 for the I. D. Code designation and the destination on the logic function
diagram (YFR) and a YL01 for the destination ID-code on the module parameter
mask of the SIM binary output module on the hardware diagram (YDR).