The hierarchical structure of TXP

Operating and
Operating and
Monitoring Level
Monitoring Level
Processing Level
Processing Level
Group Control Level
Group Control Level
Individual
Individual
Control Level
Control Level
Field Level
Field Level
This figure shows all different and possible components of TXP. Also, it shows
how they are organized in hierarchical structure.
The Individual Control Level, at the bottom, is directly connected to the
Field. There are two different configurations for this level: FUM or SIM.
The Group Control Level is responsible for the group automation tasks,
coordination of the individual controllers and communication tasks with the
Operating and Monitoring system (OM).
The Processing Level processes and stores all signals from the
Automation System and also sends the operator commands to the right
Group Control Level.
The Operating and Monitoring Level is the Man-Machine Interface of TXP.
It shows the actual status of the plant to the operator, takes data from the
Processing Level of the System and interprets the orders from operators,
sending this information to the Processing Level.
4
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
OT
OT
OT
OT
OM
OM
AP
AP
FUM-B
FUM-B
Training Center
OT/ET
OT
OT
OT/ET
ES
DS
ES
DS
AP
AP
FUM-B
FUM-B
TXP-CLC Course
OT/DT
OT/DT
S5-AG
S5 E/A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents