Bso Binary Output Signal; Abbreviations - Siemens TXP-CLC Manual

Table of Contents

Advertisement

Explanation
The block can only be used in the Group Control Level of the Automation
Processor. The CBO block can be parameterized to provide a binary output
signal on the SIM I/O module that responds to a control scheme. Below is the
parameter mask for the CBO function block followed by a brief explanation of
each output and parameter:

BSO Binary Output Signal

Binary output signal presents a high or low level voltage signal at the
output channel of the I/O module. There are no settings.
Hardware Fault
There are no channel faults associated with the CBO block.
Signal Simulation
Binary Output value of "1" indicates that the signal is simulated and not
from the process. The output simulation is set from the ES680 similar to the
FB70 BT block in chapter 7. This simulation can be used as an output from the
CBO block for other logic.
4
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.