Mod; Lv1; Lv2; Lv3 - Siemens TXP-CLC Manual

Table of Contents

Advertisement

TXP-CLC Course

MOD

This parameter defines whether the input signals are processed mathematically,
and how. Square root calculation are only used for positive values.There are 9
possible choices in the parameter mask: 0 - 8
Meaning:
0 = no modification
1 = square-rooting from 0 to 110 % (complete measuring range)
2 = square-rooting from 5 to 110 %, range 0 to 5 % = "0"
3 = square-rooting from 10 to 110 %, range 0 to 10 % = "0"
4 = Multiplication (with correction factor)
5 = Multiplication followed by square-rooting from 0 to 110 %
6 = Multiplication followed by square-rooting from 5 to 110 %
7 = Multiplication followed by square-rooting from 10 to 110 %
8 = Multiplication by square-rooted correction factor
The default setting is 0

LV1

This parameter is the limit value, in engineering units,) of the first binary output.
8

LV2

This parameter is the limit value, in engineering units, of the second binary
output.

LV3

This parameter is the limit value, in engineering units, of the third binary output.
LV4
This parameter is the limit value, in engineering units, of the fourth binary output.
HYS
This parameter defines the range, in engineering units, between triggering and
resetting of the limit signals. The default setting is 5.
ABZE
This parameter defines the sampling period for generation of the signal change
report (TTD) to the Operating and Monitoring (OM) system. A TTD is only
generated if a downward or upward violation of the delta parameter (DELT) has
occurred. The range of values that can be used are 250 to 60000.
The default setting is 1000 (1 s)
DELT
This parameter defines how much of a change of the analog input signal is
required in order for a TTD to be generated. The default setting is 0