Stagger time for restart (TWS)

Name: TWS
Function: Defines the time by which the automatic restart is delayed
(stagger times)
Range of values: 0 to 10,000
Meaning:
Basic setting:

Feed-back contact Travel limit ON (RWE)

Name: RWE
Function: Defines whether the ON feed-back message of the controlled drive can
be detected, and with which type of switch
Range of values:
Meaning:
Basic setting:

Feed-back contact Travel limit OFF (RWA)

Name: RWA
Function: Defines whether the OFF feed-back message of the controlled drive
can be detected, and with which type of switch
Range of values:
Meaning:
Basic setting:

Time for leaving of limit position (TVE)

Name: TVE
Function: Defines the maximum time for the drive to leave the a limit position
after a command output, for alarm and indication (only effective with both RWE
and RWA set at 3)
Range of values:
Meaning:
Basic setting:
14
Copying of this document, and giving it to others and use or communication of the contents, are forbidden without express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design.
0 = 0 s (no stagger time)
10,000 = 1,000 s (adjusting steps: 0.1 s)
0
0 to 4
0 = no detection/monitoring
1 = NO contact (using form A contact)
2 = NO contact using form C contact
3 = NO contact activating parameters TGL and TVE
4 = NC contact (using form B contact)
1
0 to 4
0 = no detection/monitoring
1 = NO contact (using form B contact)
2 = NO contact using form C contact
3 = NO contact activating parameters TGL and TVE
4 = NC contact (using form A contact)
1
0 to 600
0 = no run time monitoring
600 = 60 s (adjusting steps: 0.1 s)
0