Operation

With Quick Start parameter alteration complete, the SITRANS LU10 may be put into
operation. (If application or enhancement parameters are altered, operation is altered
accordingly from that indicated.)

Display

In the RUN mode, the following values and indicators may be observed.
Note that many indicators are specific to certain operating conditions and therefore, all all all all
indicators are not displayed at any given time.
indicators are not displayed at any given time
indicators are not displayed at any given time
indicators are not displayed at any given time
Transducer
Normal
Operation
Failsafe
Operation
Point in Service
Point Scanned
Transducer
Point Number
Reading
Units
Hi Alarm
Lo Alarm
Hi Hi Alarm
Lo Lo Alarm
Filling Indicator
Emptying Indicator indicates the vessel is emptying.
Bar Graph
Data In
Data Out
Auxiliary Reading
Point in Service
Point Scanned
Normal Operation
Failsafe Operation
7ML19985AN02
Point Number
Auxiliary
Reading
Siemens Milltronics Proprietary
Communications Loop
the current display pertains to a transducer measurement.
the Point Number (1 to 10) the current display pertains to.
displays the level, space, or distance (flashes error messages, if any).
the Reading is in m, cm, mm, ft, in, or %.
indicates level has risen above 80% (and not yet fallen below 75%).
indicates level has fallen below 20% (and not yet risen above 25%).
indicates level has risen above 90% (and not yet fallen below 85%).
indicates level has fallen below 10% (and not yet risen above 15%).
indicates the vessel is filling.
indicates the material level from 0 to 100%.
indicates the SITRANS LU10 is receiving data from the BIC-II (if used).
indicates the SITRANS LU10 is transmitting data to the Peripheral Communi-
cations terminals.
as selected by the keypad (terminal numbers if transducer or TS-3 is wired
wrong).
indicates the Point Numbers included in the scan sequence.
indicates the Point scanned (independent from the Point Number display).
indicates operating conditions are good and the Reading is reliable.
indicates operating conditions are poor and the Reading may be incorrect.
SITRANS LU10 – INSTRUCTION MANUAL
Units
Reading
Data In
Data Out
Priority
Point Scan
Indicator
Hi Hi Alarm
Hi Alarm
Filling/Emptying
Indicator
Bar Graph
Lo Alarm
Lo Lo Alarm
Page 23