Commissioning
10.4 Differential pressure and flow rate
10.4.4
Commissioning with vapor
①
②
③
,
④
⑤
⑥
Figure 10-2
Requirement
All valves are closed.
Procedure
Hot vapor
Danger of injury or damage to device.
If the shut-off valves
stabilizing valve
vapor.
• Follow the specified procedure for commissioning.
174
Pressure transmitter
Stabilizing valve
Differential pressure valves
Differential pressure lines
Shut-off valves
Measuring steam
WARNING
⑥
and the differential pressure valve
②
is then opened, the transmitter
⑦
Drain valve
⑧
Condensate pots
⑨
Differential pressure transducer
⑩
Insulation
③
are both open and the
①
can be damaged by the flow of
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07