Hardware Installation
Caution

4-Port Panel Mount Installation

Caution
20 - Hardware Installation
4. Verify that the Status LED has completed the boot cycle and network
connection for the DeviceMaster is functioning properly using the following
table.
The STATUS LED on the device is lit, indicating you have power and it
has completed the boot cycle.
Note: The Status LED flashes while booting and it takes approximately
STATUS
15 seconds for the Bootloader to complete the cycle. When the
Bootloader completes the cycle, the LED flashes rapidly for
several times then stays off and blinks approximately every 10
seconds when there is no PLC connection.
If the LINK (green) LED is lit, it indicates a working Ethernet
LINK
connection.
If the ACT (yellow) LED flashes, it indicates network activity.
ACT
Note: For additional LED information, go to the
Do not connect RS-422/485 devices until the IP address is configured
and an appropriate port interface type has been configured. The
default port setting is RS-232.
5. Go to
Preparing the DeviceMaster for Configuration
network settings and how to configure the DeviceMaster for use.
Use the following procedure to install the DeviceMaster 4-port.
1. Optionally, attach the mounting brackets using the screws provided in the kit
(6-32 1/4" flathead machine) or place the DeviceMaster on a stable surface.
Failure to use the correct screws can damage the PCB and void the
warranty. Do NOT use screws that exceed the length of the screws
provided with the mounting bracket kit.
Note: If you ordered the DeviceMaster Rackmount Shelf Kit accessory, use the
document that accompanied that kit or
mount the DeviceMaster on the shelf.
2. Connect the DeviceMaster to the same Ethernet network segment as the PLC.
If the DeviceMaster serial number is below xxxx-030000 use one of the
following methods to connect the cable. Serial numbers above xxxx-030000,
the Ethernet port are interchangeable.
Ethernet hub or switch (10/100Base-T): Connect to the port labeled UP
on the DeviceMaster using a standard Ethernet cable.
Server NIC (10/100Base-T): Connect to the port labeled DOWN on the
DeviceMaster using a standard Ethernet cable.
Daisy-chaining DeviceMaster units: Connect the port labeled DOWN on
the first DeviceMaster to the port labeled UP on the second DeviceMaster
or other device using a standard Ethernet cable. Refer to
DeviceMaster 4-Port Units
Note: Your model provides two Ethernet ports, UP is the first port and DOWN
is the second port.
Note: Do not connect multiple units until you have changed the default IP
address, see
Preparing the DeviceMaster for Configuration
PNIO-2304 LED Descriptions
on Page 158.
DeviceMaster PNIO | UP User Guide: 2000639 Rev. A
Status LED table
on Page 156.
on Page 23 for default
download the document
Daisy-Chaining
on Page 23