Parts Replacement; Recommended Maintenance; Battery; Ups Component Parts - Toshiba G9400 Series Installation And Operation Manual

Table of Contents

Advertisement

7

Parts Replacement

7.1 Recommended Maintenance

Toshiba International Corporation recommends the UPS have regular preventative maintenance (PM) visits to ensure
optimum operation and longevity. Toshiba recommends two Major PM's per year, at six month intervals.
A Major PM includes maintenance of the batteries and an offline inspection of the UPS. Contact Toshiba International
Corporation Service Department at 1-877-867-8773 for further details.

7.2 Battery

VRLA battery lifetime may vary according to the frequency of use and the average ambient operating temperature.
The end of battery life is defined as the state of charge resulting in an ampere-hour capacity less than, or equal to,
80% of nominal capacity.
Battery replacement is recommended if its capacity is at or below this percentage.

7.3 UPS Component Parts

UPS components have a defined life expectancy (Fans, Capacitors, Filters, etc.) Life expectancies shown are based
on normal operating conditions. Life Expectancy will shorten in more extreme operating conditions.
Contact Toshiba International Corporation for a complete parts replacement schedule. Recommended replacement
time interval varies with operating environment.
Contact Toshiba International Corporation for application specific recommendations.
Parts name
Cooling fans
Electrolytic Capacitors
AC filter Capacitors
Control Relays
Contactors
PCB
Control power supply
LCD
Fuses
Thermal relays
WARNING
G9400 480V 1200-2000kVA Installation and Operation Manual 203078-001
Table 7–1 Standard Replacement Parts List
Life Expectancy
* Periodic replacements are needed.
Any parts replacements (including modification) without authorization by Toshiba could
result in personal injuries, death, destruction of the UPS, or voiding of UPS warranty.
5 years*
Replace with new part
15 years
Replace with new part
15 years
Replace with new part
Replace with new part
15 years
Replace with new part
15 years
15 years
Replace UPS
15 years
Replace with new part
10 years*
Replace with new part
10 years*
Replace with new part
10 years*
Replace with new part
Replacing method, etc.
55