1.17.1 Specifications and Features

Specification/Feature
Integrated Voltage Regulator
Status and Shutdown Indicators
Operating Temperature
Storage Temperature
Humidity Withstand
Salt Spray Tolerance
Circuit Protection
Sensing, Nominal
Sensing Mode
Input Requirements
Continuous Output
Maximum Forcing Output
Transition Frequency
Exciter Field Resistance
No-Load to Full-Load Voltage Regulation
Thermal Drift
Response Time
System Voltage Adjust Range
Voltage Adjustment
Remote Voltage Adjustment
Paralleling Capability
VAR/PF Control Input

1.17.2 Integral Voltage Regulator

Adjustment
Voltage Adjustment
V/Hz Cut-in
Underfrequency Unload Slope
Reactive Droop
Voltage Regulator Gain Adjust
Startup Voltage Ramp Rate
1.17.3 Activator Board GM88453
(13- 32EKOZD/11- 28EFKOZD
Models)
36
Section 1 Specifications
Voltage Regulator Type Integral with Decision-Makerr 3500
5 VDC @ 100 mA max. 5.0 ADC with GM88453 Activator Board
5 VDC @100 mA max. 7.8 ADC with GM88453 Activator Board
VAR Control Mode, PF Control Mode, System VAR Control, System PF Control
Digital Display
Voltage Adjust
V/Hz Setpoint
V/Hz Slope
0- 10% of System Voltage (Volts per Cycle)
Volt Droop @
0.0% to 20% of System Voltage
100% kVAR
Voltage Gain Adjust
Startup Ramp Rate
Patented Hybrid Design
LEDs and Graphical LCD Display
- 40_C to 70_C (- 40_F to 158_F)
- 40_C to 85_C (- 40_F to 185_F)
5- 95% Condensing
5% Salt Spray per ASTM-B-117-90
Solid-State, Redundant Software and Fuses
100- 600 V (L-L), 50- 60 Hz
RMS, Single- or 3-Phase
8- 36 VDC
42.0- 62.0 Hz
4- 30 Ohms with GM88453 Activator Board
0.5%
<0.5% (- 40_C to 70_C) [- 40_F to 158_F ] Range
Less than 5mS
10%
Controller Menu Knob
0.5- 4.5 VDC (10%) Bias Input
Reactive Droop plus Load Share and Control
Range Setting
10% of System Voltage
42 to 62 Hz
1 to 255
5.0% to 100.0%/Sec
Interfaces between the controller and alternator assembly
D
using rotor field leads, auxiliary power windings, and
optic board leads.
Allows the Decision-Makerr controller the ability to
D
control a wound-field alternator using the same control
signal as the Fast Responset alternator.
Permits the generator set controller to control the current
D
to the exciter field of a wound-field excited alternator.
Contains two isolated relay driver outputs (RDO) rated at
D
250 mA. Provides RDO outputs indicating a field over-
excitation condition and that the alternator is supplying
voltage to the activator.
Default Selection
System Voltage
1.0 Hz Below Nominal Frequency
5% of Rated Voltage per Cycle
1% of System Voltage
128
25%/Sec
TP-6953
7/19

Hide quick links:

Advertisement

Table of Contents
loading