Programmable Analog Resistive Input #4, used as Digital:
Programmable Analog Resistive Input #5, used as Digital:
Programmable Analog Resistive Input #6, used as Digital:
Figure 2-23 Programmable Analog Resistive Inputs, Used as Digital Inputs
94
Section 2 Operation
Programmable Resistive Input #4 can be used as a Digital Input.
When configured as a Digital Input, it can be configured under Programmable Digital
Input 103.
NOTE: This input is not recommended for connection to devices further than 30 m
(98 ft.) from the generator set to avoid the potential damage to the sensitive resistive
input measurement circuitry.
This input is considered "Closed" when there is less than 50 Ohms of resistance
between P2 pin 12 and P1 pin 31.
If Digital Input Logic is set to "Active Close", the input becomes active when the
resistance between P2 pin 12 and P1 pin 31 (as indicated in Analog Resistive Input
Metered Relative Value) is below 50 Ohms.
If Digital Input Logic is set to "Active Open", the input becomes active when the
resistance between P2 pin 12 and P1 pin 31 is greater than 50 Ohms.
Programmable Resistive Input #5 can be used as a Digital Input.
When configured as a Digital Input, it can be configured under Programmable Digital
Input 104.
NOTE: This input is not recommended for connection to devices further than 30 m
(98 ft.) from the generator set to avoid the potential damage to the sensitive resistive
input measurement circuitry.
This input is considered "Closed" when there is less than 50 Ohms of resistance
between P2 pin 11 and P1 pin 31.
If Digital Input Logic is set to "Active Close", the input becomes active when the
resistance between P2 pin 11 and P1 pin 31 (as indicated in Analog Resistive Input
Metered Relative Value) is below 50 Ohms.
If Digital Input Logic is set to "Active Open", the input becomes active when the
resistance between P2 pin 11 and P1 pin 31 is greater than 50 Ohms.
Programmable Resistive Input #6 can be used as a Digital Input.
When configured as a Digital Input, it can be configured under Programmable Digital
Input 105.
NOTE: This input is not recommended for connection to devices further than 30 m
(98 ft.) from the generator set to avoid the potential damage to the sensitive resistive
input measurement circuitry.
This input is considered "Closed" when there is less than 50 Ohms of resistance
between P2 pin 10 and P1 pin 31.
If Digital Input Logic is set to "Active Close", the input becomes active when the
resistance between P2 pin 10 and P1 pin 31 (as indicated in Analog Resistive Input
Metered Relative Value) is below 50 Ohms.
If Digital Input Logic is set to "Active Open", the input becomes active when the
resistance between P2 pin 10 and P1 pin 31 is greater than 50 Ohms.
TP-6953
7/19