Kohler EKOZD Series Service page 83

Marine generator sets
Table of Contents

Advertisement

SiteTecht Parameter
Analog Resistive Input Metered Value
Analog Resistive Input Metered Relative Value
Analog Resistive Input Enabled
Analog Resistive Input Switch Logic
Analog Resistive Input Function
Analog Resistive Input Protectives Enabled
Analog Resistive Input Event
Analog Resistive Input Sensor
Analog Resistive Input Low Protective Inhibit Delay
Analog Resistive Input High Protective Inhibit Delay
Analog Resistive Input Delay
Analog Resistive Input Inhibit Delay
Analog Resistive Input Normal Delay
Analog Resistive Input Low Warning Delay
Analog Resistive Input Critically Low Warning Delay
Analog Resistive Input High Warning Delay
Analog Resistive Input Critically High Warning Delay
TP-6953
7/19
Write
Decision-Maker
Access
Units
User Interface
None
Measurement: ###.# Ohms
None
Always
Input Enabled: On/Off
Always
Always
Always
Low Warning: On/Off
High Warning: On/Off
Low Shutdown: On/Off
High Shutdown: On/Off
Always
Always
Sensor Type:
Always
s
Low Protect Inhibit: ##s
Always
s
High Protect Inhibit: ##s
Always
s
Always
s
Always
s
Always
s
Low Warning Delay: ##s
Always
s
Always
s
High Warning Delay: ##s
Always
s
3500
r
Notes
The current value of the
input (scaled to the units
of the function ID)
The value of the input
relative to the full range
of the input
Indicates whether this
input is enabled
The type of switch that is
connected to the input,
where "normal" refers to
the non-activated state.
Indicates the functionality
of this IO point
Indicates which of the
protectives are active for
this input
The parameter ID
defining the function for
this input
The type of sensor
connected to the input
The time, after crank
disconnect, before the
protectives for this input
are monitored; if 0,
protectives are monitored
even when the engine is
stopped
The time, after crank
disconnect, before the
protectives for this input
are monitored; if 0,
protectives are monitored
even when the engine is
stopped
The time that the input
must be active before a
status change is
indicated
The time that the input
must be active before a
status change is
indicated
The time that the input
must be within its normal
operating range before all
protectives are
considered good
The time that the input
must be within its
warning operating range
before a warning
protective is indicated
The time that the input
must be within its
warning operating range
before a warning
protective is indicated
The time that the input
must be within its
warning operating range
before a warning
protective is indicated
The time that the input
must be within its
warning operating range
before a warning
protective is indicated
Section 2 Operation
83

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents