7. Repeat steps 2- 5. Replace the FRX activator
board if it fails either test.
FN
FP
1. Flashlight
2. FRX activator board
3. Fuse (1 amp)
Figure 11-8 FRX Activator Board Test B
196 Section 11 Alternator Component Testing and Adjustment
1
2
AC1
3
AC2
4
AC3
5
6
GM98939-1-/TP- 6783-3
4. Switch DPST
5. 120 volts AC plug
6. 120 volt/100 watt lamp
11.5 Exciter Armature Test
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the alternator. Hot parts can cause severe
injury or death. Avoid touching the alternator field or exciter
armature.
When shorted, the alternator field and exciter
armature become hot enough to cause severe burns.
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
High voltage test. Hazardous voltage can cause severe
injury or death. Follow the instructions of the test equipment
manufacturer when performing high-voltage tests on the rotor
or stator. An improper test procedure can damage equipment
or lead to generator set failure.
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on
Remove the negative (- ) lead first
when disconnecting the battery.
Reconnect the negative (- ) lead last
when reconnecting the battery.
Moving parts.
the
generator
set.
TP-6953
7/19