Kohler EKOZD Series Service page 147

Marine generator sets
Table of Contents

Advertisement

Analog Resistive Input
A1
Oil Pressure (Resistive Sensor 1)
A2
Coolant Temperature (Resistive Sensor 2)
A3
Lloyd's Oil Pressure 2 (Resistive Sensor 3)
A4
High Exhaust Temperature (Resistive Sensor 4)
A5
Unused (Resistive Sensor 5)
A6
Unused (Resistive Sensor 6)
Analog Differential Input
V1P
Circuit Breaker Status P (Diff. Volt Input 1P) *
V1N
Circuit Breaker Status N (Diff. Volt Input 1N)
V2P
Voltage Bias P (Diff. Volt Input 2P) *
V2N
Voltage Bias N (Diff. Volt Input 2N)
V3P
Speed Bias P (Diff. Volt Input 3P) *
V3N
Speed Bias N (Diff. Volt Input 3N)
Digital Input
D1
Optional Low Coolant Level (Digital Input 1)
D2
Optional Low Oil Level (Digital Input 2)
D3
Optional Fuel Leak (Digital Input 3)
D4
Lloyd's High Oil Temperature (Digital Input 4)
D5
Low Seawater Pressure (Digital Input 5)
D6
Lloyd's Low Coolant Pressure (Digital Input 6)
Relay Driver Output
RDO1
Circuit Breaker Open (RDO1) *
RDO2
Circuit Breaker Close (RDO2) *
RDO3
RDO3 Cold Start
RDO4
RDO4 Relay Output
* Used for Paralleling
Figure 8-2 User Inputs/Factory-Reserved Inputs
Pin
No.
P1 Main Connector (35-Pin)
18
Oil Pressure (Resistive Sensor 1) (wire 7)
30
Coolant Temp (Resistive Sensor 2) (wire 5)
7
Speed Pickup (+) (BLU)
8
Speed Pickup (- ) (GRN)
15
Remote Start/Stop (wire 3)
14
E-Stop (wire 1)
26
E-Stop (wire 1A)
34
Digital Input 1 (wire 31)
25
Unused
22
Digital Input 2 (wire 25)
29
Current Sense CT_l1_P
17
CT_l2_P
28
CT_l3_P
16
CT_lR_N CT Return
27
Aux Shutdown / EOV (Marathon alternator)
33
Digital Input 3 (wire 64)
2
Unused
24
Controller Power (wire P1) (Battery +)
TP-6953
7/19
Pin
No.
(Continued) P1 Main Connector (35-Pin)
3
21
31
20
11
12
23
35
9
10
5
6
13
32
19
4
1
P2 Options Connector (14-Pin)
12
11
10
1
2
6
Analog Digital
3
7
A1
4
A2
8
5
14
9
13
P3 AC Sensing Connector (7-Pin)
D1
7
8
D2
4
5
2
1
6
3
D3
* Used for Paralleling
Figure 8-3 Connector (P1, P2, & P3) Designations
Controller Ground (wire N4) (Battery - )
Digital Input 4 (Lloyd's High Oil Temp)
(wire 69)
Return (Analog) Isolated Ground
(wire BGA)
Unused
COM (- ) Isolated RS485
COM (+) Isolated RS485
PGEN (- )
PGEN (+)
Isolated CAN (+) (CAN 2) (yellow)
Isolated CAN (- ) (CAN 2) (green)
Non Isolated CAN (+) (CAN 1) (yellow)
Non Isolated CAN (- )(CAN 1) (green)
Run (Battery +) (wire 70)
Digital Input 5 (Low Seawater Pressure)
Resistive Sensor 3 (Lloyd's Oil Pressure 2)
Alternator Excitation Output (wire 38)
Crank Output (line 71)
Resistive Sensor 4 (High Exhaust
Temperature)
Unused
Unused
Digital Input 6 (Lloyd's Low Coolant
Pressure)
Diff Volt Input 1P (CB Status*) BSP
Diff Volt Input 1N (CB Status*) BSN
Diff Volt Input 2P (Voltage Bias*) VBP
Diff Volt Input 2N (Voltage Bias*) VBN
Diff Volt Input 3P (Speed Bias*) SBP
Diff Volt Input 3N (Speed Bias*) SBN
RDO1 (CB Open*) CBO
RDO3 (Cold Start) N7
RDO2 (CB Close*) CBC
RDO4 (Relay Output) RD3
Bus Voltage Sensing* - L1
Bus Voltage Sensing* - L2
Bus Voltage Sensing* - L3
Gen Voltage Sensing - L3 (C)
Gen Voltage Sensing - L2 (B)
Gen Voltage Sensing - L1 (A)
Gen Voltage Sensing - L0 (NEU)
Unused
Section 8 Decision-Makerr 3500 Controller
Analog Digital
D4
D5
A3
A4
A5
A6
D6
V1P
V1N
V2P
V2N
V3P
V3N
RDO1
RDO3
RDO2
RDO4
147

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents