SiteTecht Parameter
Genset Low Voltage Shutdown Limit
Genset High Voltage Shutdown Limit
Genset Short Term Low Frequency Shutdown Delay
Genset Long Term Low Frequency Shutdown Delay
Genset High Frequency Shutdown Delay
Genset Low Frequency Shutdown Limit
Genset High Frequency Shutdown Limit
Programmable Digital Input
Digital Input Board Number
Digital Input Io Number
Digital Input Status
Digital Input Enabled
Digital Input Logic
Digital Input Function
Digital Input Event
Digital Input Delay
Digital Input Inhibit Delay
Digital Input Description
Programmable Digital Output
Digital Output Board Number
Digital Output Io Number
Digital Output Status
Digital Output Enabled
Digital Output Logic
Digital Output Function
Digital Output Event
Digital Output Description
68
Section 2 Operation
Write
Decision-Maker
Access
Units
User Interface
Always
%
Undervoltage: ##%
Always
%
Overvoltage: ##%
None
s
None
s
None
s
Always
%
Underfrequency: ##%
Always
%
Overfrequency: ##%
None
I/O Board Number: X
None
None
Always
Enabled: On/Off
Always
Always
Function:
Always
Event:
Always
s
Delay Time: ##s
Always
s
Inhibit Time: ##s
Always
Description:
None
I/O Board Number: X
Not supported for these models.
3500
r
Notes
Percentage of System
Voltage that the
generator voltage must
drop below for an under
voltage condition to be
indicated
Percentage of System
Voltage that the
generator voltage must
exceed for an over
voltage condition to be
indicated
Percentage of System
Frequency that the
generator frequency must
drop below for an under
frequency condition to be
indicated
Percentage of System
Frequency that the
generator frequency must
exceed for an over
frequency condition to be
indicated
Indicates board number
this IO point is located on
Indicates the point
number, of this IO type
on this board, for this
configuration
The current value of the
input (scaled to the units
of the function ID)
Indicates whether this
input is enabled
The type of switch that is
connected to the input,
where "normal" refers to
the non-activated state
Indicates the functionality
of this IO point
The parameter ID
defining the function for
this input
The time that the input
must be active before a
status change is
indicated
The time that the input
must be active before a
status change is
indicated
A user-defined
description of this IO
point
Indicates board number
this IO point is located on
TP-6953
7/19