Kohler EKOZD Series Service page 194

Marine generator sets
Table of Contents

Advertisement

11.4 FRX Activator Board Test
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on
Remove the negative (- ) lead first
when disconnecting the battery.
Reconnect the negative (- ) lead last
when reconnecting the battery.
Disabling the generator set.
cause severe injury or death.
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (- ) lead first. Reconnect the negative
(- ) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
194 Section 11 Alternator Component Testing and Adjustment
the
generator
set.
Accidental starting can
Before working on the
The FRX activator board is mounted on the exciter
armature and controls current flow to the alternator field.
See Figure 11-6.
1. FRX activator board
Figure 11-6 FRX Activator Board
The following test determines if the FRX activator board
is non-functional.
See Section 11.2, Alternator Troubleshooting. Examine
the photo transistor board for visible signs of damage
(open foil patterns and heat discoloration) before
testing.
To test the FRX activator board, the following
components are needed:
One 120-volt/110-watt light bulb with socket
D
Switch, DPST (double-pole/single-throw) 120 volt
D
10 amp minimum)
Fuse, 1 amp (in holder)
D
120 volt AC plug with cord
D
Five 6 mm screws and terminal nuts
D
Flashlight
D
1
GC70113B-
TP-6953
7/19