10. GENERAL TECHNICAL FEATURES.
10.1. INTERNATIONAL STANDARDS.
Quality and Environmental Management
General and safety requirements for UPS used in user access areas.
Electromagnetic compatibility (EMC) requirements for UPS
Railway standards
Method of specifying the performance and test requirements of UPS
Table 14. Standards applied.
10.2. ENVIRONMENTAL CHARACTERISTICS.
Acoustic noise at 1 metre distance
Operating altitude
Relative humidity
Operating temperature
Storage and transport temperature
Recommended battery storage temperature
Table 15. Environmental characteristics.
10.3. MECHANICAL CHARACTERISTICS.
Specifications of the cabinets
Dimensions (Depth × Width × Height)
Colour
Degree of protection, IEC60529
Sub-rack specifications
Dimensions (Depth × Width × Height)
Weight
Colour
Degree of protection, IEC60529
Power module specifications (PM)
Dimensions (Depth × Width × Height)
Weight
Colour
Specifications of Bypass and Monitoring
Module (MBS)
Dimensions (Depth × Width × Height)
Weight
Colour
Table 16. Mechanical characteristics.
52
Information
Information
Units
mm
-
-
Units
mm
Kg.
-
-
Units
mm
Kg.
-
Units
mm
Kg.
-
Units
dB(A)
masl
%
ºC
0.. 40 (battery life is reduced by 50% for every 10ºC increase over 20ºC)
ºC
ºC
24 U
33 U
888 × 639 × 1103
888 x 639 x 1613
20/10 and 30/15
671 × 485 × 308
58 ÷ 73
10 kVA
15.3
2-slot and 4-slot sub-racks
395 × 485 × 130
4.5
Standards
ISO 9001 & ISO 14001
IEC/EN62040-1
EN-IEC 62040-2
EN 50121-4 / EN 50121-5
VFI-IEC-111 (EN-IEC 62040-3)
Environmental
56.0
2400
0.. 95%, non-condensing
-20.. +70 (UPS)
0.. 25 (20ºC for optimum storage)
42 U
888 x 639 x 2013
RAL 9005
IP20
40/10 and 45/15
60/10 and 90/15
671 × 485 × 485
792 × 485 × 1033
66 ÷ 112
RAL 9005
IP20
15 kVA
590 × 485 × 85
15.5
RAL 9005
6-slot sub-rack
380 × 485 × 380
13.5
RAL 9005
UPS
Bat.
Yes
Yes
100 ÷ 178
SALICRU
Need help?