Salicru ADAPT User Manual

Salicru ADAPT User Manual

Modules 25-300 kva iii/iii

Advertisement

Quick Links

USER'S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Modules 25-300 kVA III/III
ADAPT

Advertisement

Table of Contents
loading

Summary of Contents for Salicru ADAPT

  • Page 1 USER'S MANUAL UNINTERRUPTIBLE POWER SUPPLY (UPS) Modules 25-300 kVA III/III ADAPT...
  • Page 2 8.2.5. Switching the UPS into Normal Mode from Maintenance 5.2.2. Unpacking Power Module Bypass Mode 6. POSITIONING 8.3. BATTERY MAINTENANCE 6.1. POSITIONING CABINET 8.4. EPO 6.2. INSTALLING POWER MODULE 8.5. INSTALLATION OF PARALLEL OPERATION SYSTEM 6.3. BATTERY 6.4. CABLE ENTRY SALICRU...
  • Page 3 10.3. MECHANICAL CHARACTERISTIC 10.4. ELECTRICAL CHARACTERISTICS 10.4.1. Electrical Characteristics (Input Rectifier) 10.4.2. Electrical Characteristics (Intermediate DC Link) 10.4.3. Electrical Characteristics (Inverter Output) 10.4.4. Electrical Characteristics (Bypass Mains Input) 10.5. EFFICIENCY 10.6. DISPLAY AND INTERFACE USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 4: Acknowledgement Letter

    We remain at you entire disposal for any further information or any query you should wish to make. Yours sincerely. SALICRU The equipment here described can cause important • physical damages due to wrong handling. This is why, the installation, maintenance and/or fixing of itself must be done by our staff or qualified personnel exclusively.
  • Page 5: Information For Safety

    CD-ROM documentation in a safe place with easy access. The following terms are used in the document indistinctly to be referred to: «ADAPT, unit or UPS».- Uninterruptible Power Supply. • Depending on the context of the sentence, it can be re-...
  • Page 6: Quality And Standard Guarantee

    In case of any modification or intervention over the equip- ment by the end-user, the manufacturer is not responsible. WARNING!: SLC ADAPT. This is a category C3 UPS product. This is a product for commercial and industrial application in the second environment - installation restrictions or additional measures may be needed to prevent distur- bances.
  • Page 7: System Configuration

    With the function of Battery cold start, the UPS may start without utility. See more detail in section 8.1.2. Battery mode • Bypass mode • Maintenance mode (manual bypass) • ECO mode • Auto-restart mode • Frequency Converter mode • USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 8: Eco Mode

    UPS Structure Battery Charger DC/DC Fig. 6. Maintenance mode operation diagram Danger: During Maintenance mode, dangerous voltages are present on the terminal of input, output and neutral, even with all the mod- ules and the LCD turned off. SALICRU...
  • Page 9 Fig. 9. System outlook-Front view. 1- Front Door 2- Dust Filter 3- Back Door 4- Foot Print Fig. 8. System outlook of UPS. 1- System Connectors 2- Power module connector Fig. 10. System outlook-Rears View. USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 10: Installation Instruction

    The most suitable storage temperature is 20 ºC to 25ºC. 5.1.3. Size and Weight ≥800 The size of three views for the UPS cabinet is shown in Fig. 11. Fig. 12. Room reserved for the cabinet (Unit: mm) SALICRU...
  • Page 11: Unloading And Unpacking

    (see Fig. 14). The packing case must be placed on the platform smoothly, as is shown in Fig. 16. Fig. 16. Place on platform smoothly Fig. 14. Disassemble the case USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 12 2- Foam packing 3- Power module Fig. 18. Remove the foam cover. Take out the UPS with plastic package and dismantle the packaging materials. Attention: The waste materials of unpacking should be disposed to meet the demand for environmental protection. SALICRU...
  • Page 13: Installing Power Module

    5- 1# Power module 6- Mounting holes weight over a larger area. For instance, cover the floor with iron plate or increase the supporting area of the anchor bolts. Fig. 20. Installing power module USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 14 2- Power Cables 3- Blanking plate Ensure the positive, negative, neutral electrode is correctly con- Fig. 22. Cable entry nected from the battery unit terminals to the breaker and from the breaker to the UPS system. SALICRU...
  • Page 15: Power Cables

    Warning : Tighten the connections terminals to enough torque mo- • ment, and please ensure correct phase rotation. The grounding cable and neutral cable must be connected • in accordance with local and national codes. USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 16: Control And Communication Cables

    J2-1 TEMP_BAT Detection of battery temperature J2-2 TEMP_COM common terminal AUX-N.O. J3-1 ENV_TEMP Detection of AUX-N.O. environmental temperature J3-2 TEMP_COM common terminal Generator Table 4. Description of J2 and J3. Fig. 27. Diagram of aux. contact external manual bypass SALICRU...
  • Page 17 The interface diagram is shown in Fig. 29, and descrip- J9-2 GENERAL_ALARM_NO Integrated warning relay tion is shown in Table 8. (normally open) will be closed during warning J9-3 GENERAL_ALARM_ Common terminal Table 9. General alarm dry contact interface description. USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 18 SNMP: Used on site installation for communication (Optional). Intelligent card interface: Extension dry contact interface (Optional). SALICRU...
  • Page 19: Lcd Panel For Power Module

    Status indicator, control and operation keys and LCD -> Enable Module “OFF” Key display. ;2)Press the “OFF” key for 3 seconds, the power module quits from the system.; Pressing the FUNC keys resets the LCD display. USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 20 • Fault and warning codes are shown in Digit Displays Area in recycle (shown with short dash when less than 3).The meanings of the codes are listed in Table 12. SALICRU...
  • Page 21 System output not supplied by inverter, inverter fault for at least one module. Flashing red System output supplied by inverter, inverter fault for at least one module. Battery and battery converter normal, battery not charging USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 22 The energy flow mimics the flow of the power. the back of the door to enable ,see Fig.5.2) Long press, transfer to the inverter MUTE Long press to switch between turning off and on the buzzing Table 15. Functions of Control and operation keys SALICRU...
  • Page 23 , (At the bottom left of the screen), and the system enters the page of the Cabinet, as it is shown in Fig. 36. 1- Running status, 2- Version information, 3- Title, 4- Information display, 5- Submenu Fig. 36. Cabinet USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 24 The interface of each submenu is shown from Fig. 37 to Fig. 40. Fig. 40. Submenu interface of Cabinet: Interface of Battery Fig. 37. Submenu interface of Cabinet: Interface of Main Fig. 38. Submenu interface of Cabinet: Interface of Output SALICRU...
  • Page 25 Submenu • The submenu includes Input, Output, Load, INFO. and S-CODE. Users can enter the interface of each submenu by directly touching the icon .Each interface of the submenu is shown in Fig. 42. USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 26 Fig. 44. Module menu: Interface of Information Inlet Temperature(°C) Inlet Temperature of the selected power module Outlet Temperature(°C) Outlet Temperature of the selected power module S-code Fault Code For the maintenance personne Table 17. Description of each submenu of Module SALICRU...
  • Page 27 The “C” stands for Ampere number. For instance, if the bat- • tery is 100AH, then C=100A.. Warning: Ensure the number of the battery set is completely in accord with the practice, otherwise, it will cause serious damage to the batteries or the equipment. USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 28 System Mode Setting the system mode: Single ,parallel, Single ECO, parallel ECO,LBS, parallel LBS RATE Configure the rated Parameter For the factory use CONFIGURE Configure the system For the factory use Table 18. Description of each submenu of Setting SALICRU...
  • Page 29 Output Short Circuit-Clear Incident above disappears Battery EOD-Set Battery End Of Discharge Battery EOD-Clear Incident above disappears Battery Test-Set Battery Test Starts Battery Test OK-Set Battery Test OK Battery Test Fail-Set Battery Test fails USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 30 (a)Green, an event occurs: (b)Grey, the event occurs then Manual Shutdown-Set N# Power Module Manually clears: (c)Yellow, warning occurs: (d) Red, faults happen. Shutdown Manual Boost Charge-Set Manually Battery Boost Charge Manual Float Charge-Set Manually Battery Float Charge SALICRU...
  • Page 31: Test Command

    , (At the bottom right of the Enable the switch for powering off the Power Module by screen), and the system enters the page of the Operate, as it is shown in Fig.49. touching the icon USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 32 Touch the icon to display the 3 phase output current. • Touch the icon to display the 3 phase bypass voltage. • Touch the icon to zoom in the wave. • Touch the icon to zoom out wave. • SALICRU...
  • Page 33: Ups Start-Up

    UPS starts charging the battery. The LED Close the external output power supply isolation to supply indicators are listed below in Table 23. the load, and the system is working on battery model. USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 34 Turn off the maintenance bypass switch and the load is powered through bypass. The rectifier starts followed by Warning: the inverter. Ensure the bypass is working normally before transferring to After 60S, the system transfers to Normal mode. bypass mode. Or it may cause failure. SALICRU...
  • Page 35: Battery Maintenance

    When the EPO is triggered, the load is not powered by the UPS. “BATTERY “page of the Setting (See Fig.54), Set the period Be careful to use the EPO function. time in the item “Auto Maintenance Discharge Period” and confirm. 1- EPO BUTTON Fig. 54. EPO USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 36: Installation Of Parallel Operation System

    Fig. 55. Parallel diagram The parallel board is located at the back of the UPS cabinet, whose name is PS1203-TF4 as is shown in Fig. 56. Zoom A AREA Parallel board PS1203-TF4 Fig. 56. Location of the Parallel board SALICRU...
  • Page 37 Fig. 57. Fig. 57. Parallel connection For more details of parallel operation, please refer to the “In- struction for Parallel Operation of Modular UPS”. USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 38: Maintenance

    Follow the steps below to maintain the bypass module. Transfer the system to bypass mode through the LCD con- trol panel (see section 7.6.5). Close maintenance bypass switch, the UPS power will be supplied by maintenance bypass. SALICRU...
  • Page 39 防尘网 固定条 1- Dust filter 2- Bracket Fig. 58. Dust filter on the back side of front door USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 40: Product Specification

    10.3. MECHANICAL CHARACTERISTIC Item Unit 150/30 300/30 Mechanical Dimension 600*1100*2000 W×D×H Weight Color Black Protection Level (IEC60529) IP20 Table 26. Mechanical Characteristics for Cabinet Item Unit Parameter Mechanical Dimension, W×D×H 460×790×134 Weight Table 27. Mechanical Characteristics for Power Module SALICRU...
  • Page 41: Electrical Characteristics

    Battery Charge V/ cell 2.4V/cell(selectable from : 2.3V/cell~2.45V/cell) Constant current and constant voltage charge mode Battery Charging Power Max Current 10%* UPS capacity (selectable from : 0~20% * UPS capacity) Table 29. Battery USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 42 Synchronized Range Settable ±0.5Hz~±5Hz, default ±3Hz Table 31. Bypass Mains Input 10.5. EFFICIENCY Item Unit Value Normal mode(dual conversion) >95 ECO Mode Battery discharging efficiency (battery at nominal voltage 480Vdc and full-rated linear load) battery mode >95 Table 32. Efficiency SALICRU...
  • Page 43: Display And Interface

    10.6. DISPLAY AND INTERFACE Item Value Display LED + LCD +Color touch screen Interface Standard:RS232, RS485, USB, Dry Contact Option: SNMP,AS/400 Table 33. Display and Interface USER'S MANUAL ADAPT UNINTERRUPTIBLE POWER SUPPLY...
  • Page 44 Avda. de la Serra 100 08460 Palautordera BARCELONA Tel. +34 93 848 24 00 Fax +34 93 848 22 05 services@salicru.com SALICRU.COM The Technical Service & Support (T.S.S.) network, Commercial network and warranty information are available in website: www.salicru.com Product Range...