UNINTERRUPTIBLE POWER SUPPLY (UPS) + LIGHTING FLOW DIMMER STABILIZERS (ILUEST) + SWITCH MODE POWER SUPPLY + STATIC INVERTERS + PHOTOVOLTAIC INVERTERS + VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS
Summary of Contents for Salicru SLC TWIN PRO series
Page 1
UNINTERRUPTIBLE POWER SUPPLY (UPS) + LIGHTING FLOW DIMMER STABILIZERS (ILUEST) + SWITCH MODE POWER SUPPLY + STATIC INVERTERS + PHOTOVOLTAIC INVERTERS + VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS UNINTERRUPTIBLE POWER SUPPLY UPS SLC TWIN PRO series 0.7 to 3 kVA...
5.1.3. Start up the UPS, with no AC mains (Battery mode) 5.1.4. UPS shutdown with AC mains (on Inverter mode). 5.1.5. UPS shutdown with no AC mains (on Battery mode). 5.1.6. Battery test function. 5.1.7. Alarm silencer. 5.1.8. EPO (Emergency Power Output). SALICRU...
Yours sincerely. • «Earth bonding terminal». Connect the earth cable coming from the load and the external battery cabinet to SALICRU this terminal. • Preservation of the environment: The presence of The equipment here described can cause important this symbol in the product or in their associated docu- physical damages due to wrong handling.
Low Voltage Electro- technical Regulations or standards of the country. Type of circuit is selectable through the LCD panel of the equipment. The contact is preset from factory as normally Use approved cables only SALICRU...
open, so the button must be switched to close the circuit and The UPS has to be completely dry before starting any instal- the voltage to the loads is broken. To establish the power lation task. supply to the loads again, the EPO button must be deacti- • Do not store, install or expose the equipment in corrosive, vated.
«User’s manual». • When the equipment and/or battery module has a protec- tion through a fuse and it were needed to be replaced, it will always be done by another one with the same dimension, type and size. SALICRU...
Quality and standard 2.3. Environment. guarantee. This product has been designed to respect the environment and has been manufactured in accordance with the standard ISO 14001. 2.1. Declaration of the management. Equipment recycling at the end of its useful life: Our company commits to use the services of authorised socie- Our target is the client’s satisfaction, therefore this Management ties and according to the regulations, in order to treat the recov-...
Figures regarding its main features or specifications can be checked in the nameplate of the equipment. Keep them in mind for its installation. Models from 0.7 and 1 kVA Models from 1.5 to 3 kVA Fig. 1. Front view from 0.7 to 3 kVA models. SALICRU...
Page 10
Protection Protection cover for cover for smart slot smart slot Extended autonomy connector Input Input breaker breaker protection protection Transient Transient Output Output protection protection sockets sockets Input socket Input socket (*) Transient protection (fax, modem,...) Models from 0.7 and 1 kVA (standard) Models from 0.7 and 1 kVA (B1) Fig.
Page 11
Output Output terminals terminals Input socket Input terminals Transient protection (*) Transient protection (*) (*) Transient protection (fax, modem,...) Model from 3 kVA (standard) Model from 3 kVA (B1) Fig. 4. Rear view from 3 kVA model. SALICRU...
Page 12
Battery module for models 0.7 and 1 kVA Battery module for models 1.5 from 3 kVA Fig. 5. Front view from battery module. Connector for UPS (extended autonomy) Earthing screw connection Connector connection Connector to another for UPS module (extended autonomy) Earthing screw...
Under request is possible to supply the acces- sories (screws and electrical cables), needed to install and connect the batteries. For equipments requested with no batteries, the acquisi- tion and connection of them will always be done by the customer and under his responsibility. SALICRU...
The isolation transformer can be installed at the input or output • True on-line double conversion and independent output fre- of the UPS from SLC TWIN PRO series and it will always be quency from mains. located out from the equipment enclosure.
One of the most used industrial standard protocols in the market is the MODBUS protocol. SLC TWIN PRO series is also ready to be integrated in this type of environments through the external “SNMP TH card” device with MODBUS protocol.
Installation. transformer, as standard, as an option or either installed by yourself, either at the UPS input line, output or in both, protec- tions against indirect contact has to be fitted in (residual cur- rent device) at the output of each transformer, because due to its specification of isolation it will prevent the triggering of • Check the Safety instructions, from section 1.2.3.
UPS by the use of a forklift, pallet structions of this manual, the labelling will always prevail. truck or by means of the most suitable means of transport by evaluating the remoteness of the location point. SALICRU...
4.3.2. Connection to output. Minimum features of fast Batteries type • As this is a device with class I protection against Model x Nº) = element Voltage Current electric shocks, it is essential to install a protective nominal floating DC (V) earth conductor (connect earth( )).
4.3.6. Communication ports. 4.3.6.1. USB interface. • Communication line (COM) is a very low voltage circuit of safety. To preserve the quality, it has to be installed separate from other lines that have dangerous voltages (energy SALICRU...
• Installation procedure: Go to website: SW2 "On" http://support.salicru.com Relays interface card SW1 (*) Choose the operating platform that you need and follow the instructions described in the web site to download the software. When downloading the needed files from Internet, enter...
«OFF» (see table 4). To start up the UPS press front panel for more than 1 second. over the key «ON» (see table 4). The UPS will shift to no output mode «0» -bypass deactivated- SALICRU...
Control panel with LCD. Display Function Input information It displays the input voltage value, which will be showed from 0 to 999 Vac It displays the frequency value of the input voltage, which 6.1. Control panel. will be showed from 0 to 99 Hz It displays that the input voltage is higher than the SPEC range and the UPS runs on battery mode.
6.2.3. Line mode. The LCD panel on line mode is shown in figure 14. The infor- mation about mains, battery, UPS output and load will be dis- played. The UPS operating code is «2». In the same figure that the «INVERTER» stage is displayed (frame with INVERTER inscription inside) and active, it means that the inverter is supplying the used power by the load/s and at the same time the batteries are being charged.
Fig. 16. Steps 1 to 4: Example of how to set the figures of an equip- ment. Step 1: A blinking black dot appears beside the 208V figure after pressing the key « » (Select) of the LCD panel, for more than 1 sec.. SALICRU...
• Pay attention to the safety instructions regarding battery and • Date when the problem occurred. the stated in section 1.2.3.3. • The UPSs from SLC TWIN PRO series only requires a • Complete description of the problem, including the informa- minimum maintenance. The used battery in the standard tion given by the LCD panel and the status of the alarms.
Make sure that the short-circuit has Inverter short-circuit. Short-circuited output. been cancelled and the UPS doesn't have any internal fault before starting up the equipment again. Bus short-circuit UPS internal fault. Contact with the S.T.S.. Table 7. Troubleshooting guide. Other circumstances or conditions. SALICRU...
• Check the fan status. 7.3.1. Covered product. • Bypass test. UPS SLC TWIN PRO series. • Make a general cleaning of the equipment. • Controlling the mechanical parts and temperatures. 7.3.2. Warranty terms. This way, it is guaranteed the perfect operating and the possible This product is guaranteed against any parts and/or labour de- coming faults are avoided.
12 V DC / 7 Ah Quantity of batteries in serial / set voltage 3 / 36 V DC 8 / 96 V DC Low battery voltage, block / set 11.4 V DC / 34.2 V DC 11.4 V DC / 91.2 V DC SALICRU...
Available powers (kVA / kW) 0.7 / 0.56 1 / 0.8 1.5/ 1.2 2 / 1.6 3 / 2.4 End battery voltage: - From 0-30 % load, block / set 10.7 V DC / 32.1 V DC 10.7 V DC / 85.6 V DC - From 30-70 % load, block / set 10,2 V DC / 30.6 V DC 10.2 V DC / 81.6 V DC...
Page 31
This lack of linearity affects to the wave shape, because the equipment has introduced harmonics that they were not in the input signal. As they are harmonics, it means multiple of the input signal, this distortion is not so dissonant and it is more difficult to detect. SALICRU...