Salicru SLC ADAPT2 Series User Manual page 48

Hide thumbs Also See for SLC ADAPT2 Series:
Table of Contents

Advertisement

7.5.2. Table of UPS Warnings
No.
1
WRN_BATTERY_NOT_CONNECTED
2
WRN_MODULE_ON_LESS
3
WRN_UTILITY_ABNORMAL
4
WRN_BYPASS_VOLT_ABNORMAL_R
5
WRN_BYPASS_VOLT_ABNORMAL_S
6
WRN_BYPASS_VOLT_ABNORMAL_T
7
WRN_BYPASS_MODULE_OVER_LOAD_R
8
WRN_BYPASS_MODULE_OVER_LOAD_S
9
WRN_BYPASS_MODULE_OVER_LOAD_T
10
WRN_BYP_FREQ_OVER_TRACK
11
WRN_EXCEED_TX_TIMES_LMT
12
WRN_BATTERY_VOLT_LOW
13
WRN_LOST_N_X_REDUNDANT
14
WRN_BATTERY_TEST_FAIL
15
WRN_BATTERY_MAINTENANCE_FAIL
16
WRN_AMBIENT_OVER_TEMP
17
WRN_INPUT_VOLT_DETECT_FAIL
18
WRN_OUTLET_TEMP_ERROR
19
WRN_DC_BUS_OVER_VOLT
20
WRN_INLET_OVER_TEMP
21
WRN_BATTERY_OVER_TEMP
22
WRN_BYPASS_FAN_EXPIRED
23
WRN_CAPACITOR_EXPIRED
24
WRN_FAN_EXPIRED
25
WRN_OUTLET_DELTA_TEMP
26
WRN_BATTERY_EXPIRED
27
WRN_DUST_FILTER_EXPIRED
28
WRN_BYPASS_OVER_TEMP
29
WRN_RTC_BATT_LOW
48
NAME OF ALARM
DESCRIPTION
Battery disconnected
There are not enough Modules to supply the Inverter load
Rectifier Input voltage out of range
Bypass voltage out of range in Phase R
Bypass voltage out of range in Phase S
Bypass voltage out of range in Phase T
Bypass overload in Phase R
Bypass overload in Phase S
Bypass overload in Phase T
Modules and Bypass Synchronisation fault
Bypass transfer attempts exceeded
Battery voltage low
Loss of Redundancy
Battery Test results in Fail
Discharge Test results in Fail
Ambient overtemperature
Rectifier input voltage fault
Error in outlet air temperature measurement
DC bus overvoltage
Module inlet air over-temperature
Battery over-temperature
Excess Operating Time of the fans in the Bypass
Excess Operating Time of the capacitors in the Modules
Excess Operating Time of the fans in the Modules
Internal over-temperature
Excess Battery Operating Time
Excess Dust Filter Operating Time
Bypass over-temperature
Low voltage in Lithium battery of the clock and Non-volatile
Memory
TYPE OF ALARM
UPS
UPS
MODULE
UPS
UPS
UPS
UPS
UPS
UPS
UPS
MODULE
MODULE
UPS
MODULE
MODULE
UPS
MODULE
UPS
MODULE
MODULE
UPS
UPS
MODULE
MODULE
MODULE
UPS
UPS
UPS
UPS
SALICRU

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SLC ADAPT2 Series and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents