Data Storage (cont'd)
Galaxy Dimension Installer Manual

Using Storage Mode

On the Legacy panel, enter and leave Engineer mode, so the External RS232 module is recognised. Then re-
enter Engineer mode to use the storage mode facilities.
On the Legacy panel, enter menu 56.2.4=Communications.RS232.Copy/Overwrite.
To copy the programming data FROM the Legacy panel TO the Grade 3 panel, select 1=Copy Site. To
copy the programming data FROM the Grade 3 panel TO the Legacy panel, select 2=Overwrite Site.
Press 1 to start the copy procedure, or 2 to abort at any time. The copy procedure can also be aborted by
pressing esc on the Dimension panel; this exits Storage mode.
NOTE: The copy procedure is started as soon as the option is selected; neither panel requests confirmation
before proceeding.
During the copy procedure, the display on the affected keypad on the Dimension panel will show a message
indicating which data elements are being copied (Users, Parameters, etc).

Leaving Storage Mode

At any time, Storage mode can be exited by pressing esc on the Dimension panel. It is recommended that the
panels be separated before this is done, although doing so is not necessary. If the panels remain connected
while the Dimension panel is not in Storage mode, behaviour on line 2 of the Dimension panel and line 1 of the
Legacy panel cannot be guaranteed.
E-2