Meaning of the three digit error codes / test mode

A three digit error code is displayed in the display in case of a failure of an intelligent fire detector. The meanings
of these codes and measures for correcting the error condition are given in the following table.
Error indication in case of detector replacement
During detector replacement, the display shows error codes which have to comply with the modifications done.
If error messages remain after the detector replacement has been completed the cause of the trouble can be
identified quickly with the help of the 3 digit error code (ref. tables below).
Trouble
Possible cause
Code No.
001
002
Detector is faulty.
003
Strong electromagnetic
004
disturbances or detector
faulty.
Ambient light too bright at
005
location where detector is
installed.
006
Detector is contaminated
007
or moist.
008
Strong electromagnetic
disturbances of the visual
009
sensor in the area of
8 - 60 kHz (  50 V / m).
1)
An electrically leading
substance caused a short-
circuit in the I-chamber.
2)
CO sensor is overloaded
with a high CO
010
concentration.
3)
Strongly pulsed high
frequency fields.
4)
Short circuit on the CO
sensor.
1)
Detector is contaminated
with dust or similar.
011
2)
CO sensor is faulty.
FB 798951.10.GB0 / 04.15
Fire Alarm Control Panel IQ8Control C / M
1st. measure
Exchange detector.
Check the detector with
programming software tools
8000, check installation place
if necessary.
Check whether detector is
exposed to source of bright
light. Change location if
necessary.
Clean detector and check with
tools 8000.
Disturbance is caused by an
electrical consumer in
immediate proximity of the
detector. Moving detector if
necessary.
Clean I-chamber and check it
with programming software
tools 8000. Noticing salt or
fraying deposits.
Check if the detector is
exposed to a high CO load. If
necessary, reset the detector
and recheck. The CO sensor
should have at least 15
minutes to return to its
quiescent values before
rechecking. Check the CO
concentration at the location
of the detector and move the
detector if necessary.
If necessary, check
installation location.
Replace detector.
Clean detector and check it
with programming software
tools 8000.
Replace detector.
2nd. measure
Return faulty detector to
manufacture.
Return detector for controlling
to manufacture.
If fault re-occurs on this
detector, detector should be
returned to manufacture for
inspection.
---
One coupling of the
disturbance about the record
circuit. Checks whether record
circuit was transferred
parallely to power lines.
Replace detector and return
to manufacture.
Return faulty detectors to the
manufacturer.
Return detector to
manufacturer for checking.
Return faulty detectors to the
manufacturer.
Using another detector type.
Return faulty detectors to the
manufacturer.
115