29 = Online Level
The On-line Level parameter determines the level of events that are printed when parameter 28 = Online
Print is enabled:
0 (default) - basic print (setting, unsetting, alarms);
1
- full print excluding MAX events (setting, unsetting, alarms, modifications, technical
details)
2
- full print including MAX events (all logged events).
3
- MAX events only (only card events).
4
- Basic Print plus MAX events (option 0 + MAX events).
30 = Video
This parameter determines the number of activations that must occur on any of the zones programmed as
Video, in a single set period, before a full alarm occurs; there is no time limit on the period between
activations. The Video parameter is programmable within the range 1–9 activations; the default is 2. The video
output occurs on every activation but a full alarm does not occur until the programmed number of activations is
reached. The Video zones activation counter is reset when the system is unset.
NOTE: The activations of the Video zones are cumulative - the counter is incremented each time any Video
zone in the group is activated.
This parameter can be assigned a different value for each group.
31 = Delay Alarm
This parameter determines the delay between the activation of an Intruder Delay zone and the alarm sound-
ing or a Log Delay zone being recorded as opening in the event log. The Delay Alarm is programmable
within the range 0–3000 seconds; the default is 60.
If a second Intruder Delay zone opens followed by the first zone closing, the Delay Alarm time continues to
count from the activation of the first zone. The Delay Alarm timer is reset only when all delay type zones
return to the closed state.
This parameter can be assigned a different value for each group.
32 = Show Alarms
If the Show Alarms parameter is enabled, the first alarm activation is immediately displayed on all the
keypads when an alarm condition occurs. Normally alarm messages are not displayed until the alarm is
cancelled by entry of a valid code. Parameter 51.63, Banner Alerts must be enabled to view alarms on the
keypad banner.
0 = disabled (default)
1 = enabled
NOTE: This parameter will only function when at least one group is unset.