52 - Program Zones (cont'd)
30 Intruder Delay
The Intruder Delay function is identical to the Intruder function, with the exception that the full alarm activa-
tion can be delayed for up to 50 minutes (0–3000 seconds); this is determined by the Delay Alarm param-
eter (option 51.31). The Intruder Delay zone must remain open for the period of the Delay Alarm param-
eter; while the zone is open the Entry/Exit Horns activate to remind the user that the Delay Alarm is count-
ing down. Unsetting the system or closing the Intruder Delay zone aborts the alarm and resets the timer.
If a second Intruder Delay zone opens followed by the first zone closing, the Delay Alarm time continues to
count from the activation of the first zone. The Delay Alarm timer is reset only when all delay type zones
return to the closed state.
31 Log Delay
The Log Delay function operation is identical to the Log function, with the exception that the recording of the
zone activation can be delayed for up to 50 minutes (0–3000 seconds); this is determined by the Delay
Alarm parameter (option 51.31). Closing the Log Delay zone resets the timer and aborts the recording of
the event in the log.
32 Set Log
The Set Log function is identical to the Log function, with the exception that zone activations are only re-
corded in the event log during the set period.
33 Custom A
The Custom A function allows a zone to be assembled. The functionality of the zone; when it activates; the
outputs activated; if it sets or unsets the systems; if it logs, are assigned using menu option 64 = ASSEMBLE
ZONE. Once the Custom A zone has been created, it can be assigned to as many zones as required.
34 Custom B
This function is identical in operation and assembly to Custom A.
6-83