Malfunctions During Power Operation-Digital Display - Kessel Ecolift Installation And Operating Manual

Electrical components
Table of Contents

Advertisement

Available languages

Available languages

Error display
Cause
Maximum number of pump
Power – LED is on
Alarm – LED and
activations has been excee-
Pump – LED blink
ded
alternatingly
Power – LED is on
Maximum pump operation
Alarm – LED and
hours has been exceeded
Pump – LED blink
simultaneously
Level error:
Power – LED is on
Alarm – LED blinks
- indicates possible improper
optical sensor installation
- Too much wastewater ente-
ring Ecolift's integrated
floor drain

5.2 Malfunctions during power operation-digital display

Error display
5. Malfunctions
Corrective action
Replace pump
Contact KESSEL Customer
Service Partner
- Reduce amount of wastewater
entering Ecolift
- Check to make sure optical
sensor has been properly
connected to control unit
Cause
Corrective action
Unplug control unit, disconnect
Battery is not connec-
batteries and replace with new
ted or defective
batteries if required. If the control
unit is now operational, the con-
trol unit's LEDs will display this.
Unplug control unit and dis-
- Commissioning:
connect batteries. Check to
Motor cable not
make sure motor cable is pro-
properly connected or
perly connected, replace motor if
damaged
necessary.
- Operation:
Motor
cable defective or
motor is defective
Unplug control unit and dis-
Commissioning: Motor
optical sensor cable
connect batteries. Check to
not properly connected
make sure motor optical sensor
or damaged
cable is properly connected, re-
Operation: Motor opti-
place motor optical sensor if ne-
cal sensor cable defec-
tive or sensor is dama-
cessary.
ged
Commissioning: Pump
Unplug control unit and dis-
power cable not pro-
connect batteries. Check to
perly connected or da-
make sure motor cable is pro-
maged
perly connected, replace motor if
Operation: Pump power
necessary
cable defective or pump
is damaged
39
Advice
Lifespan of pump has been ex-
ceeded
Pump runs too often in short
periods of time
- Check to make sure optical sen-
sor is screwed to red marked
connection
- Check to make sure motor
sensor is connected all the way
to the right
Advice
- Commissioning: the Ecolift can be pla-
ced into operation even if there is a
problem with the batteries – the alarm
notification can be acknowledged
- Operation: The battery fault alarm will
sound within 5 minutes. The system is
fully operational. Manual operation is
also possible.
This error will only be detected in
operational mode (see Section 8.2
'Additional Functions')
Comssioning: Commissioning is not
possible with this error
Operation: The error will be detected
during backwater or by manually ac-
tivating a test cycle on the control unit
The optical sensor cable is automa-
tically checked every 2 seconds
This error will only be detected in
operational mode (see Section 8.2
'Additional Functions')
Commissioning: Commissioning is
not possible with this error
Operation: The error will be detected
during backwater or by manually ac-
tivating a test cycle on the control unit