2.2.3 Configuration of remote I/O communication

The S10VE system can use an RI/O-IF module to perform remote I/O communication on a maximum of two
lines (see Figure 2-3).
The maximum length of each line is 300 m by remote I/O cable alone, extendable to a maximum of 3.3 km
using remote I/O optical adapters. This length of 3.3 km is three optical cables of 1 km each, plus the 300 m
achievable by remote I/O cable.
You can use HSC-1000 and HSC-2100 PI/O units in the same system.
PI/O unit
PS
ST
RI/O
(RI/O)
opti-
ADP
PI/O unit
PS
ST
RI/O
(RI/O)
opti-
ADP

Figure 2-3 Configuration of remote I/O communication

S10VE CPU unit
PS
RI/O-IF
CPU
PI/O unit
I/O
PS
ST
(RI/O)
cal
PI/O unit
ST
I/O
PS
(RI/O)
cal
Specifications for remote I/O communication by RI/O-IF module
• Number of lines: Two lines per module
• Number of modules: One per unit
• Cable length: Maximum 300 m
• Number of connected PI/O units: 12 per channel
Specifications when RI/O optical ADP is integrated with RI/O-IF module
• Cable length of optical cable segments: 1 km per segment
• Number of optical segments per channel: 3 segments per channel