Table 13-19 Error Codes For Communication Errors - Hitachi S10VE User Manual

Table of Contents

Advertisement

13. Troubleshooting
(b) Return code errors
When a J.NET module detects an error on the communications line, the module sets the ALM of the S
register and the error flag of the NET status to ON. The module then writes an error code in the S table
to record the error information.
Error code
7110
An undefined service was requested.
7120
The data length is incorrect.
7130
The packet structure is incorrect.
7061
Input data has not been completely acquired by
the station.
2010
An error occurs during a CRC check.
2020
The station number is between 128 and 254.
The station number of the receiver is incorrect.
2030
An undefined service was specified.
2040
I frame length is 137 bytes or longer, and UI
frame length is 134 bytes or longer.
2041
An I frame is not included in the I response.
2042
An I frame is included in the monitoring frame.
2050
There is an error in the data link procedure.
2060
A timeout occurred (no response was received
from the slave device within the specified
time).
2061
Recovery was not possible after retries.
2070
A frame could not be transmitted to the
network. Alternatively, an error was detected
while a frame was being received.
2080
A miscellaneous error occurred.

Table 13-19 Error codes for communication errors

Description
- Reset the CPU. If the error occurs after the
reset, restart the system.
- If the error persists, replace the J.NET module.
- This is not an error.
- The module returns to normal as soon as the
input data is completely acquired.
- Verify that the network status is normal.
- Verify that the SVPT settings match the station
settings.
- If the error persists, replace the J.NET module.
- Turn off and then turn on the power to the
station.
- Verify that the switch settings of the J.NET
module and the station are correct.
- If the error persists, replace the station.
- Check the network line connection and the
termination resistor connection.
- Verify that the SVPT settings match the station
settings.
- Reset the CPU. If the error occurs after the
reset, restart the system.
- If the error persists, replace the J.NET module.
- Reset the CPU. If the error occurs after the
reset, restart the system.
- If the error persists, replace the J.NET module.
13-38