(2) Troubleshooting user programs
Check the BASE SYSTEM/S10VE error log, and then follow the instructions in Table 13-10 to
troubleshoot the problem.
Contents of the BASE SYSTEM/S10VE error log
No.
Error code
1
03030000
Program error (Inst. Alignment
Error)
2
03040000
Program error (Illegal Instruction)
3
03080000
Program error (Privileged
Instruction)
4
03390000
Program error (FP Program Error)
5
03400000
Program error (Instruction Page
Fault)
6
03420000
Program error (Invalid Inst. Access) Instruction access error
7
03460000
Program error (Inst. Access
Protection)
8
03470000
Program error (Data Alignment
Error)
9
03600000
Program error (Data Page Fault)
10 03620000
Program error (Invalid Data Access) Data access error
11 03660000
Program error (Data Access
Protection)
12 03B70001
System Bus Error (S10 Bus
DTACK Timeout)
13 03D00001
Ladder Program error (Data Access
Protection)
14 03D01208
Ladder Program error (N-Coil
Nesting Over)
15 03D0120C
Ladder Program error (Illegal
Function Parameter)
16 03D01210
Ladder Program error (Ladder Area
Sum Mismatch)
Macro parameter error
17 05110000

Table 13-10 User program troubleshooting (1/2)

Error message
Description
Instruction alignment error
Illegal instruction error
Privileged instruction error
Floating-point calculation error
Instruction access page fault
Instruction access protect error
Data alignment error
Data access page fault
Data access protect error
Timeout detected when the CPU
accessed the S10 bus
Data access protect error
N coil overflow error
System operation function
parameter error
Ladder area SUM error
Macro parameter error
13-17
13. Troubleshooting
Recovery
operation
Check and review
#1
the user tasks.
No action is
required. (This is
not an error.)
Check and correct
the ladder program.
Reload the ladder
program.
Check and review
#1
the user tasks.

Advertisement