Online Menu: Remote Restart; Figure 8-81 Remote Restart Confirmation Message; Figure 8-82 Restart Successful Message; Figure 8-83 Restart Failed Message - Hitachi S10VE User Manual

Table of Contents

Advertisement

8.4.3.6 Online menu: Remote Restart

Use this menu item to restart stopped PCs in RUN mode.
Confirm the following before performing a remote restart:
- The PADT is not connected to an ET.NET module.
You can remotely restart a CPU module whose CPU RUN/STOP switch is set to STOP. However, the
CPU module will not restart in RUN mode. The CPU module will enter RUN mode when you switch its
CPU RUN/STOP switch to RUN.
(1) From the main menu, select Online and then Remote Restart.
You cannot perform a remote restart if the communication type is ET.NET. If you attempt to do so, an
error message appears indicating that the function cannot be used when BASE SYSTEM is connected
to an ET.NET module (Figure 8-50).
(2) A message appears asking you to confirm that you want to restart the PCs. To restart the CPU module,
click OK.

Figure 8-81 Remote restart confirmation message

(3) The system restarts the CPU module. If the restart is successful, the system displays a message to that
effect. Click OK to dismiss the message. You are returned to the BASE SYSTEM main window
(Figure 8-14).
If the restart fails, the system displays a message reporting that the restart was not successful. Click
OK to dismiss the message. In this case, you will need to restart the CPU module by turning it off and
then on again.

Figure 8-82 Restart successful message

Figure 8-83 Restart failed message

8-69
8. Tools

Advertisement