Figure 13-24 Remote I/O Optical Adapter Failure Locations; Table 13-36 Analyzing Failures From Remote I/O Optical Adapter Leds - Hitachi S10VE User Manual

Table of Contents

Advertisement

13. Troubleshooting
Troubleshooting from the remote I/O optical adapter LEDs
When creating the remote I/O optical adapter connection configuration depicted in Figure 13-24, identify the
location of the failure by using the combination of LED status for the remote I/O optical adapter.
Failure location: RI/O-IF to RI/O
(a) optical ADP
RI/O
IF

Table 13-36 Analyzing failures from remote I/O optical adapter LEDs

No.
Failure location
OPT
TX
1
No failure Normal ON ON ON ON ON ON ON ON
2
OFF OFF OFF OFF OFF OFF OFF OFF
A failure occurred
3
in the cabling
between the RI/O-
4
IF and RI/O
optical ADP (a), a
5
ON OFF OFF ON OFF ON OFF OFF Check the rotary switch settings of the RI/O optical ADP (a).
cable, or a module
6
OFF --
7
--
8
An error occurred
in the optical
ON OFF OFF ON
9
cable.
10
11
ON OFF OFF ON
A failure occurred
in the cabling
between the I/O
12
optical ADP (b)
and ST3, a cable,
13
ON ON OFF ON ON ON OFF OFF Check the rotary switch settings of the RI/O optical ADP (b).
or a module.
14
--
15
--
ON: LED on, OFF: LED off, --: No relation to LED status
RI/O
Opti
ST1
cal
ADP

Figure 13-24 Remote I/O optical adapter failure locations

LED status of the
LED status of the
RI/O optical ADP
RI/O optical ADP
(a)
OPT
RIO
RIO
OPT
OPT
RX
TX
RX
TX
RX
--
ON --
--
ON OFF --
--
--
OFF OFF OFF OFF
ON ON ON ON
OFF OFF OFF OFF
OFF ON ON OFF
--
--
--
OFF --
--
--
--
--
ON OFF --
Failure location:
Optical cable
RI/O
Opti
ADP
ST1 to ST3: Remote I/O station modules
RI/O optical ADP (a), (b): Remote I/O optical adapter
(b)
RIO
RIO
TX
RX
The location of the failure cannot be determined from the LEDs.
Return to the troubleshooting flow in Figure 13-21, and investigate
the failure according to the instructions in Nos. 2 through 15.
An error might be present in the remote I/O cable.
Check the connection of the remote I/O cable and the termination
resistor.
There might be a problem with the power of the unit in which the
RI/O optical ADP (a) is installed. Check the power status.
An error might be present in the RI/O-IF module.
Investigate the RI/O-IF module.
An error exists in the RI/O optical ADP (a). Replace the RI/O
--
--
optical ADP (a).
An error exists in the RI/O optical ADP (a). Replace the RI/O
--
--
optical ADP (a).
An error might be present in the optical cable.
Verify the optical cable and the connection.
There might be a problem with the power of the unit in which the
RI/O optical ADP (b) is installed. Check the power status.
An error might be present in the remote I/O cable.
Check the connection of the remote I/O cable and the termination
resistor.
An error might be present in the station module.
Check the status and power of the station module.
An error exists in the RI/O optical ADP (b). Replace the RI/O
--
ON
optical ADP (b).
An error exists in the RI/O optical ADP (b). Replace the RI/O
optical ADP (b).
13-90
Failure location: RI/O optical
ADP (b) to ST
ST2
cal
Corrective action
ST3

Advertisement