Commissioning the device
4.4 Configuring the device
Procedure
Proceed as follows:
1. Use "Properties" to open the "MPI" or "PROFIBUS" dialog.
2. If there are several masters connected on the bus, deactivate the "Panel is the only
3. Enter the bus address for the HMI device under "Address".
4. Select the transfer speed under "Transmission Rate".
5. Enter the highest station address on the bus under "Highest Station Address" or "Highest
6. PROFIBUS only: Select the desired profile under "Profile".
7. Confirm your entries with "OK".
Result
The MPI/PROFIBUS DP settings of the HMI device have been changed.
See also
Configuring the data channel (Page 113)
Reference for functions (Page 79)
116
master on the bus" check box.
NOTICE
The bus address in the "Address" text box must be unique throughout the
MPI/PROFIBUS DP network.
Station.
Use "Bus Parameters" to view the profile data.
NOTICE
The bus parameters must be the same for all stations in the MPI/PROFIBUS DP
network.
Operating Instructions, 03/2012, A5E03404994-02