4.
3.13.4
Output
By default, the output is configured as a Lock. When access is granted, this
output unlocks the door. This output is deactivated when the Unlock door
for timer expires, or the door contact input becomes active.
Configure the output
1.
2.
3.
TX3 Nano Configuration Manual
Copyright 2019
Active state. Active state is the state in which the input is considered
active. Select one of the following:
Close (default)
Open
There are some restrictions in configuring the active state depending on
what kind of supervision is required.
If the input is not supervised the input is either 'open' or 'closed'. If the
input is supervised for 'open' the active state cannot be 'open'.
If the input is supervised for both 'open' and 'short' the active state cannot
be 'open'.
Circuit supervision. Circuit supervision specifies the circuit
type and indicates whether the input is supervised. Select one of the
following:
None (default)
Open circuit
Short circuit
Open and short circuit
For more information on active state and supervision, see LT-6637 TX3
Nano Installation Manual on www.mircom.com.
Delay. This specifies the amount of time in seconds before the input
generates an active event. The default is 0 seconds.
Click Save Changes at the top of the window.
Click Nano Settings in the left pane.
Click the Inputs & Outputs tab at the top of the window.
Select Output1 and provide the following information:
Label. Type a name for this output.
Assigned to. Select a function for this input:
TX3 Nano Settings