Operating Guide | VLT® HVAC Basic Drive FC 101
From software version 4.0x and later (production week 33 2017 and after), the variable speed heat sink cooling fan function is
implemented in the drive for power sizes 22 kW (30 hp) 400 V IP20 and below, 18.5 kW (25 hp) 400 V IP54 and below, and 11 kW (15 hp)
200 V IP20 and below. This function requires software and hardware updates and introduces restrictions with regards to backwards
compatibility for H1–H5 and I2–I4 enclosure sizes. Refer to the following table for the limitations.
Table 2: Software and Hardware Compatibility
Software compatibility
Old software (OSS-file version 3.xx and be-
low)
New software (OSS-file version 4.xx or
higher)
Hardware compatibility
Old power card (production week 33 2017
or before)
New power card (production week 34 2017
or after)

1.5 Certificates and Approvals

Table 3: Certificates and Approvals
Certification
EC Declaration of Conformity
UL Listed
RCM
EAC
UkrSEPRO
The drive complies with UL 508C thermal memory retention requirements. For more information, refer to the section Motor Thermal
Protection in the product-specific design guide.
Danfoss A/S © 2019.11
Old control card (production week 33
2017 or before)
Yes
No
Old control card (production week 33
2017 or before)
Yes (only software version 3.xx or below)
Yes (MUST update software to version 3.xx
or below, the fan continuously runs at full
speed)
089
Introduction
New control card (production week
34 2017 or after)
No
Yes
New control card (production week
34 2017 or after)
Yes (MUST update software to ver-
sion 4.xx or higher)
Yes (only software version 4.xx or
higher)
IP20
IP54
AQ275641848264en-000101 / 132R0078| 7