Operating Guide | VLT® HVAC Basic Drive FC 101
Parameter
Option
Parameter 4-19
0.0–400.0 Hz
Max Output
Frequency
Parameter 5-40
See parameter 5-40 Function
Function Relay
Relay.
Parameter 5-40
See parameter 5-40 Function
Function Relay
Relay.
Parameter 6-10
0.00–10.00 V
Terminal 53
Low Voltage
Parameter 6-11
0.00–10.00 V
Terminal 53
High Voltage
Parameter 6-12
0.00–20.00 mA
Terminal 53
Low Current
Parameter 6-13
0.00–20.00 mA
Terminal 53
High Current
Parameter 6-19
[0] Current
Terminal 53
mode
[1] Voltage
Parameter
[0] Off
30-22 Locked
Rotor Detection
[1] On
Parameter
0.05–1 s
30-23 Locked
Rotor Detection
Time [s]
Danfoss A/S © 2019.11
Default
Usage
100 Hz
Enter the maximum output frequency value. If parameter 4-19
Max Output Frequency is set lower than parameter 4-14 Motor
Speed High Limit [Hz], parameter 4-14 Motor Speed High Limit
[Hz] is set equal to parameter 4-19 Max Output Frequency auto-
matically.
[9] Alarm
Select the function to control output relay 1.
[5] Drive run-
Select the function to control output relay 2.
ning
0.07 V
Enter the voltage that corresponds to the low reference value.
10 V
Enter the voltage that corresponds to the high reference val-
ue.
4 mA
Enter the current that corresponds to the low reference value.
20 mA
Enter the current that corresponds to the high reference val-
ue.
[1] Voltage
Select if terminal 53 is used for current or voltage input.
[0] Off
0.10 s
Programming
AQ275641848264en-000101 / 132R0078| 47