Operating Guide | VLT® HVAC Basic Drive FC 101
The dimensions are only for the physical units. When installing in an application, allow space above and below the units for cooling.
The amount of space for free air passage is listed in

3.2 Electrical Installation

3.2.1 Electrical Installation in General

All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors are
required. 75 °C (167 °F) is recommended.
Table 9: Tightening Torques for Enclosure Sizes H1–H8, 3x200–240 V & 3x380–480 V
Power [kW (hp)]
Enclo‐
IP class
3x200–240 V
sure
size
H1
IP20
0.25–1.5
(0.33–2)
H2
IP20
2.2 (3)
H3
IP20
3.7 (5)
H4
IP20
5.5–7.5
(7.5–10)
H5
IP20
11 (15)
H6
IP20
15–18.5
(20–25)
H7
IP20
22–30 (30–40)
H7
IP20
H8
IP20
37–45 (50–60)
1
2
Cable dimensions >95 mm
.
Table 10: Tightening Torques for Enclosure Sizes I2–I8
Power [kW (hp)]
Enclosure
IP class
3x380–480 V
size
I2
IP54
0.75–4.0 (1–5)
I3
IP54
5.5–7.5 (7.5–10)
I4
IP54
11–18.5 (15–25)
I6
IP54
22–37 (30–50)
I7
IP54
45–55 (60–70)
Danfoss A/S © 2019.11
3.1.1 Side-by-side
Installation.
Torque [Nm (in-lb)]
3x380–480 V
Mains
0.37–1.5
0.8 (7)
(0.5–2)
2.2–4.0 (3–5)
0.8 (7)
5.5–7.5 (7.5–10)
0.8 (7)
11–15
1.2 (11)
(15–20)
18.5–22 (25–30)
1.2 (11)
30–45
4.5 (40)
(40–60)
55 (70)
10 (89)
75 (100)
14 (124)
90 (125)
(1)
24 (212)
Torque [Nm (in-lb)]
Mains
Motor
0.8 (7)
0.8 (7)
0.8 (7)
0.8 (7)
1.2 (11)
1.2 (11)
4.5 (40)
4.5 (40)
10 (89)
10 (89)
Motor
DC con‐
Control
nection
terminals
0.8 (7)
0.8 (7)
0.5 (4)
0.8 (7)
0.8 (7)
0.5 (4)
0.8 (7)
0.8 (7)
0.5 (4)
1.2 (11)
1.2 (11)
0.5 (4)
1.2 (11)
1.2 (11)
0.5 (4)
4.5 (40)
0.5 (4)
10 (89)
0.5 (4)
14 (124)
0.5 (4)
0.5 (4)
(1)
24 (212)
DC connec‐
Control ter‐
tion
minals
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.5 (4)
0.5 (4)
AQ275641848264en-000101 / 132R0078| 15
Installation
Ground
Relay
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
Ground
Relay
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
3 (27)
0.6 (5)
3 (27)
0.6 (5)