Operating Guide | VLT® HVAC Basic Drive FC 101
Parameter
Range
Parameter 1-45
0.000–1000.000 mH
q-axis Induc-
tance Sat.
(LqSat)
Parameter 1-46
20–200%
Position Detec-
tion Gain
Parameter 1-48
20–200%
Current at Min
Inductance for
d-axis
Parameter 1-49
20–200%
Current at Min
Inductance for
q-axis
Parameter 1-70
[0] Rotor Detection
PM Start Mode
[1] Parking
Parameter 1-73
[0] Disabled
Flying Start
[1] Enabled
Parameter 3-02
-4999.000–4999.000
Minimum Ref-
erence
Parameter 3-03
-4999.000–4999.000
Maximum Ref-
erence
Parameter 3-10
-100–100%
Preset Refer-
ence
Parameter 3-41
0.05–3600.0 s
Ramp 1 Ramp
Up Time
Parameter 3-42
0.05–3600.0 s
Ramp 1 Ramp
Down Time
Parameter 4-12
0.0–400.0 Hz
Motor Speed
Low Limit [Hz]
Parameter 4-14
0.0–400.0 Hz
Motor Speed
High Limit [Hz]
Danfoss A/S © 2019.11
Default
Usage
Size related
This parameter corresponds to the inductance saturation of
Lq. Ideally, this parameter has the same value as parameter
1-38 q-axis Inductance (Lq). However, if the motor supplier
provides an induction curve, enter the induction value, which
is 200% of the nominal current.
100%
Adjusts the height of the test pulse during position detection
at start.
100%
Enter the inductance saturation point.
100%
This parameter specifies the saturation curve of the d- and q-
inductance values. From 20–100% of this parameter, the in-
ductances are linearly approximated due to parameter 1-37 d-
axis Inductance (Ld), parameter 1-38 q-axis Inductance (Lq), pa-
rameter 1-44 d-axis Inductance Sat. (LdSat), and parameter 1-45
q-axis Inductance Sat. (LqSat).
[0] Rotor De-
Select the PM motor start mode.
tection
[0] Disabled
Select [1] Enabled to enable the drive to catch a spinning mo-
tor in, for example, fan applications. When PM is selected, this
parameter is enabled.
0
The minimum reference is the lowest value obtainable by
summing all references.
50
The maximum reference is the highest value obtainable by
summing all references.
0
Enter the setpoint.
Size related
Ramp-up time from 0 to rated parameter 1-23 Motor Frequen-
cy for asynchronous motors. Ramp-up time from 0 to parame-
ter 1-25 Motor Nominal Speed for PM motors.
Size related
Ramp-down time from rated parameter 1-23 Motor Frequency
to 0 for asynchronous motors. Ramp-down time from param-
eter 1-25 Motor Nominal Speed to 0 for PM motors.
0.0 Hz
Enter the minimum limit for low speed.
100 Hz
Enter the minimum limit for high speed.
Programming
AQ275641848264en-000101 / 132R0078| 53