3.2.4.5 Recommendation of Fuses and Circuit Breakers
In the event of malfunction, failure to follow the protection recommendation may result in damage to the drive.
Table 12: Fuses and Circuit Breakers
Circuit breaker
UL
Power [kW
(hp)]
3x200–240 V
IP20
0.25 (0.33)
–
0.37 (0.5)
0.75 (1)
1.5 (2)
2.2 (3)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
Cutler-Hammer
EGE3100FFG
18.5 (25)
22 (30)
Cutler-Hammer
JGE3150FFG
30 (40)
37 (50)
Cutler-Hammer
JGE3200FFG
45 (60)
3x380–480 V
IP20
32 | Danfoss A/S © 2019.11
N O T I C E
Fuse
Non-UL
UL
Bussmann
Type RK5
–
FRS-R-10
FRS-R-10
FRS-R-10
FRS-R-10
FRS-R-15
FRS-R-25
FRS-R-50
FRS-R-50
FRS-R-80
Moeller NZMB1-
FRS-R-100
A125
FRS-R-100
Moeller NZMB1-
FRS-R-150
A160
FRS-R-150
Moeller NZMB1-
FRS-R-200
A200
FRS-R-200
Bussmann
Bussmann
Type RK1
Type J
KTN-R10
JKS-10
KTN-R10
JKS-10
KTN-R10
JKS-10
KTN-R10
JKS-10
KTN-R15
JKS-15
KTN-R25
JKS-25
KTN-R50
JKS-50
KTN-R50
JKS-50
KTN-R80
JKS-80
KTN-R100
JKS-100
KTN-R100
JKS-100
KTN-R150
JKS-150
KTN-R150
JKS-150
KTN-R200
JKS-200
KTN-R200
JKS-200
AQ275641848264en-000101 / 132R0078
Installation
Non-UL
Bussmann
Maxi‐
mum
fuse
Type T
Type G
JJN-10
10
JJN-10
10
JJN-10
10
JJN-10
10
JJN-15
16
JJN-25
25
JJN-50
50
JJN-50
50
JJN-80
65
JJN-100
125
JJN-100
125
JJN-150
160
JJN-150
160
JJN-200
200
JJN-200
200
Need help?
Do you have a question about the VLT HVAC Basic Drive FC 101 and is the answer not in the manual?