Operating Guide | VLT® HVAC Basic Drive FC 101
Parameter
Option
Parameter 1-45
0.000–1000.000 mH
q-axis Induc-
tance Sat.
(LqSat)
Parameter 1-46
20–200%
Position Detec-
tion Gain
Parameter 1-48
20–200%
Current at Min
Inductance for
d-axis
Parameter 1-49
20–200%
Current at Min
Inductance for
q-axis
Parameter 1-70
[0] Rotor Detection
PM Start Mode
[1] Parking
Parameter 1-73
[0] Disabled
Flying Start
[1] Enabled
Parameter 3-02
-4999.000–4999.000
Minimum Ref-
erence
Parameter 3-03
-4999.000–4999.000
Maximum Ref-
erence
Parameter 3-41
0.05–3600.00 s
Ramp 1 Ramp
Up Time
Parameter 3-42
0.05–3600.00 s
Ramp 1 Ramp
Down Time
Parameter 4-12
0.0–400.0 Hz
Motor Speed
Low Limit [Hz]
Parameter 4-14
0.0–400.0 Hz
Motor Speed
High Limit [Hz]
46 | Danfoss A/S © 2019.11
Default
Usage
Size related
This parameter corresponds to the inductance saturation of
Lq. Ideally, this parameter has the same value as parameter
1-38 q-axis Inductance (Lq). However, if the motor supplier
provides an induction curve, enter the induction value, which
is 200% of the nominal current.
100%
Adjusts the height of the test pulse during position detection
at start.
100%
Enter the inductance saturation point.
100%
This parameter specifies the saturation curve of the d- and q-
inductance values. From 20–100% of this parameter, the in-
ductances are linearly approximated due to parameter 1-37 d-
axis Inductance (Ld), parameter 1-38 q-axis Inductance (Lq), pa-
rameter 1-44 d-axis Inductance Sat. (LdSat), and parameter 1-45
q-axis Inductance Sat. (LqSat).
[0] Rotor De-
Select the PM motor start mode.
tection
[0] Disabled
Select [1] Enabled to enable the drive to catch a motor spin-
ning due to mains drop-out. Select [0] Disabled if this function
is not required. When this parameter is set to [1] Enabled, pa-
rameter 1-71 Start Delay and parameter 1-72 Start Function are
not functional. Parameter 1-73 Flying Start is active in VVC
mode only.
0
The minimum reference is the lowest value obtainable by
summing all references.
50
The maximum reference is the lowest obtainable by summing
all references.
Size related
If asynchronous motor is selected, the ramp-up time is from 0
to rated parameter 1-23 Motor Frequency. If PM motor is selec-
ted, the ramp-up time is from 0 to parameter 1-25 Motor Nom-
inal Speed.
Size related
For asynchronous motors, the ramp-down time is from rated
parameter 1-23 Motor Frequency to 0. For PM motors, the
ramp-down time is from parameter 1-25 Motor Nominal Speed
to 0.
0 Hz
Enter the minimum limit for low speed.
100 Hz
Enter the maximum limit for high speed.
Programming
AQ275641848264en-000101 / 132R0078
+