Operating Guide | VLT® HVAC Basic Drive FC 101
5 Warnings and Alarms
5.1 List of Warnings and Alarms
Table 19: Warnings and Alarms
Fault
Alarm/
Fault text
num‐
warning
ber
bit num‐
ber
2
16
Live zero er-
ror
4
14
Mains ph.
loss
7
11
DC over volt
8
10
DC under volt
9
9
Inverter over-
load
10
8
Motor ETR
over
11
7
Motor th over
13
5
Over Current
14
2
Earth Fault
16
12
Short Circuit
17
4
Ctrl. word TO
24
50
Fan Fault
30
19
U phase loss
31
20
V phase loss
32
21
W phase loss
38
17
Internal fault
44
28
Earth Fault
46
33
Control Volt-
age Fault
Danfoss A/S © 2019.11
Warn‐
Alarm
Trip
ing
locked
X
X
–
X
X
X
X
X
–
X
X
–
X
X
–
X
X
–
X
X
–
X
X
X
–
X
X
–
X
X
X
X
–
X
X
–
–
X
X
–
X
X
–
X
X
–
X
X
–
X
X
–
X
X
Cause of problem
Signal on terminal 53 or 54 is less than 50% of the value
set in parameter 6-10 Terminal 53 Low Voltage, parameter
6-12 Terminal 53 Low Current, parameter 6-20 Terminal 54
Low Voltage, or parameter 6-22 Terminal 54 Low Current.
See also parameter group 6-0* Analog I/O Mode.
Missing phase on the supply side or too high voltage im-
balance. Check the supply voltage. See parameter 14-12
Function at Mains Imbalance.
DC-link voltage exceeds the limit.
DC-link voltage drops below voltage warning low-limit.
More than 100% load for a long time.
Motor is too hot due to more than 100% load for a long
time. See parameter 1-90 Motor Thermal Protection.
Thermistor or thermistor connection is disconnected. See
parameter 1-90 Motor Thermal Protection.
Inverter peak current limit is exceeded.
Discharge from output phases to ground.
Short circuit in motor or on motor terminals.
No communication to drive. See parameter group 8-0*
General Settings.
The heat sink cooling fan is not working (only on 400 V,
30–90 kW units).
Motor phase U is missing. Check the phase. See parame-
ter 4-58 Missing Motor Phase Function.
Motor phase V is missing. Check the phase. See parame-
ter 4-58 Missing Motor Phase Function.
Motor phase W is missing. Check the phase. See parame-
ter 4-58 Missing Motor Phase Function.
Contact the local Danfoss supplier.
Discharge from output phases to ground, using the value
of parameter 15-31 InternalFaultReason if possible.
Control voltage is low. Contact the local Danfoss supplier.