Operating Guide | VLT® HVAC Basic Drive FC 101
Parameter
Range
Parameter 1-45
0.000–1000.000 mH
q-axis Induc-
tance Sat.
(LqSat)
Parameter 1-46
20–200%
Position Detec-
tion Gain
Parameter 1-48
20–200%
Current at Min
Inductance for
d-axis
Parameter 1-49
20–200%
Current at Min
Inductance for
q-axis
Parameter 1-70
[0] Rotor Detection
PM Start Mode
[1] Parking
Parameter 1-73
[0] Disabled
Flying Start
[1] Enabled
Parameter 3-41
0.05–3600.0 s
Ramp 1 Ramp
Up Time
Parameter 3-42
0.05–3600.0 s
Ramp 1 Ramp
Down Time
Parameter 4-12
0.0–400.0 Hz
Motor Speed
Low Limit [Hz]
Parameter 4-14
0.0–400.0 Hz
Motor Speed
High Limit [Hz]
Parameter 4-19
0.0–400.0 Hz
Max Output
Frequency
Parameter
[0] Off
30-22 Locked
Rotor Detection
[1] On
Parameter
0.05–1.00 s
30-23 Locked
Rotor Detection
Time [s]
Danfoss A/S © 2019.11
Default
Usage
Size related
This parameter corresponds to the inductance saturation of
Lq. Ideally, this parameter has the same value as parameter
1-38 q-axis Inductance (Lq). However, if the motor supplier
provides an induction curve, enter the induction value, which
is 200% of the nominal current.
100%
Adjusts the height of the test pulse during position detection
at start.
100%
Enter the inductance saturation point.
100%
This parameter specifies the saturation curve of the d- and q-
inductance values. From 20–100% of this parameter, the in-
ductances are linearly approximated due to parameter 1-37 d-
axis Inductance (Ld), parameter 1-38 q-axis Inductance (Lq), pa-
rameter 1-44 d-axis Inductance Sat. (LdSat), and parameter 1-45
q-axis Inductance Sat. (LqSat).
[0] Rotor De-
Select the PM motor start mode.
tection
[0] Disabled
Select [1] Enabled to enable the drive to catch a spinning mo-
tor.
Size related
Ramp-up time from 0 to rated parameter 1-23 Motor Frequen-
cy.
Size related
Ramp-down time from rated parameter 1-23 Motor Frequency
to 0.
0.0 Hz
Enter the minimum limit for low speed.
100.0 Hz
Enter the maximum limit for high speed.
100.0 Hz
Enter the maximum output frequency value. If parameter 4-19
Max Output Frequency is set lower than parameter 4-14 Motor
Speed High Limit [Hz], parameter 4-14 Motor Speed High Limit
[Hz] is set equal to parameter 4-19 Max Output Frequency auto-
matically.
[0] Off
0.10 s
Programming
AQ275641848264en-000101 / 132R0078| 59