CAS CI-6000A Series Manual page 57

Table of Contents

Advertisement

■ Output/input is controlled according as the program of an indicator in utomatic
program control mode.
■ External input and output signal is as follows.
1. Press TARE key so that the display shows 0kg (NET weight).
2. START INPUT: FIRST, SECOND, THIRD output is ON when START key is pressed.
3. FIRST OUTPUT (Optional preliminary) :
It is OFF when the net weight is greater than the weight
(Final - Optional preliminary).
4. SECOND OUTPUT (Preliminary) :
It is OFF when the net weight is greater than the weight (Final - Preliminary).
5. THIRD OUTPUT (Final) :
It is OFF when the net weight is greater than the weight (Final - Free fall).
6. HIGH LIMIT OUTPUT :
It is ON when the net weight is greater than the weight (Final + High limit)
after third output is ON.
7. LOW LIMIT OUTPUT :
It is ON when the net weight is greater than the weight (Final - Low limit)
after third output is ON.
8. FINISH SIGNAL :
When weight is stable, It is ON after passing the certain time of start delay.
(You can set start delay time in set mode, F21.)
It is OFF after passing the certain time of operating delay or Finish Signal OFF
Range (F22). (You can set operating delay time in set mode, F19.)
9. ZERO BAND OUTPUT :
It is ON when gross weight is lower than zero band value.
10. Discharge gate control signal could not be supplied in CI-6000A.
- Use FINISH SIGNAL OUTPUT.
11. Data Output : Data is outputted after finish signal is outputted.
12. Prepare for next batching operation.
58

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents