CAS CI-6000A Series Manual page 53

Table of Contents

Advertisement

■ You can operate external control for your needs in user program control mode.
■ External input and output signal is as follows.
1. Press TARE key so that the display shows 0kg (NET weight).
2. FIRST OUTPUT(Optional preliminary) :
It is ON when the net weight is greater than the weight
(Final - Optional preliminary).
3. SECOND OUTPUT(Preliminary) :
It is ON when the net weight is greater than the weight (Final - Preliminary).
4. THIRD OUTPUT(Final) :
It is ON when the net weight is greater than the weight (Final - Free fall).
5. HIGH LIMIT OUTPUT :
It is ON when the net weight is greater than the weight (Final + High limit)
after third output is ON.
6. LOW LIMIT OUTPUT :
It is ON when the net weight is greater than the weight (Final - Low limit)
after third output is ON.
7. FINISH SIGNAL :
When weight is stable, It is ON after passing the certain time of start delay
(You can set start delay time in set mode, F21.)
It is OFF after passing the certain time of operating delay or Finish Signal OFF
Range (F22). (You can set operating delay time in set mode, F19.)
8. ZERO BAND OUTPUT :
It is ON when gross weight is lower than zero band value.
9. Discharge gate control signal is not supplied in CI-6000A.
- Use FINISH SIGNAL OUTPUT.
10. Prepare for next batching operation.
54

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents