■ Switch setting

Fixing or Flexibility
SW4
Fixing
0
When you use the Fixing Mode (SW4=SW5=0),
you have to set one(1) of the SW1 & SW2 and
you have to set the values what you want to out in the SET MODE (F57 & F58)
Fixing or Flexibility
SW4
Flexibility
1
When you use the Flexibility Mode (SW4=SW5=1),
you select to set the setting switches what you want to out
If the output current is not correct, you need to adjust the volume resistors of VR1 & VR2.
VR1 is used to adjust to zero value. VR2 is used to adjust to Max. value.
Setting
SW5
SW1
SW2
0
1
1
Setting
SW5
SW1
SW2
1
1
1
0
1
1
0
68
SW1
SW2
1
1
0
1
1
0
Set Mode
F57(Min)
F58(Max)
4000
20000
0000
20000
0000
24000
Set Mode
F57(Min)
F58(Max)
0000
24000
Output
0 – 24mA
0 – 20mA
4 – 20mA
Output
Current
4 – 20mA
0 – 20mA
0 – 24mA
Output
Current
0 – 24mA
0 – 20mA
4 – 20mA