Figure 2.6 Output Voltage Connector With Shield - Xantrex XFR 7.5-140 Operating Manual

Xfr 1200 watt series programmable dc power supply
Hide thumbs Also See for XFR 7.5-140:
Table of Contents

Advertisement

The 60 V to 600 V (high voltage) models have a 4-terminal, wire clamp output
connector. See inset of Figure 2.6 for a labelled drawing of the wire clamp connector.
The units are shipped with a protective shield attached (see Figure 2.6). To prepare
and connect the load wiring:
3. Use a gloved finger or a blunt tool to push in the circular knockout on the right
side (recommended) of the shield. After you push in the knockout, twist it until
it detaches from the shield, and discard.
4. Insert the bushing of the small black strain relief, screw-side out, through the
knockout hole, pushing in from the outside of the shield. You will hear a snap as
the strain relief attaches securely to the shield.
5. Strip insulation 0.35" (9 mm) at the end of each of the wires.
6. Loosen the strain relief screw and route the wires through the strain relief.
7. Loosen the connector terminal screw (see inset in Figure 2.6), insert the stripped
wire into the terminal, and tighten the terminal screw securely.
8. Ensure that the wires are not pulled too taut between the terminals and the strain
relief. Tighten the strain relief screw.
Shield

Figure 2.6 Output Voltage Connector with Shield

(For 60 V to 600 V models.)
Release 3.1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Strain Relief Screw
Strain Relief
Terminal
Screws
+
Knockout
Output Voltage Connector For 60 V to 600 V Models
Installation
Load Connection
Stripped
Load Wires
0.35" (9 mm)
3 2 1
: 4
S / N
_
T :
O P
U T
T P
O U
D C
Negative
Output/Return (−)
Load Wires
Positive Output (+)
49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents