Features and Specifications
Additional Electrical Specifications
Additional Electrical Specifications
Voltage Mode Transient Response
(Time for the output voltage to
recover within 0.5% of its
previous level after a step change
in load current of up to 50% of the
rated output.)
Time delay from power on until
output stable
Input Conditions
Rated AC Input Voltage
Maximum AC Input Rating
Operational AC Input Voltage
Range
Maximum Input Current
Input Frequency Range
Power Factor
26
1 ms
4 s maximum
100/120/200/220/230/240 Vac (nominal)
1300 VA
85-250 Vac; power factor corrected.
Derate maximum output power to 900 W for
AC input less than 95 V.
13 A maximum at 100 Vac,
11 A maximum at 120 Vac,
6 A maximum at 220 Vac.
47
63 Hz
–
0.99 minimum for full load and 120 Vac
input
Operating Manual for XHR Series Power Supply